12

PROGRAMMING DEVICES

The  functional  parameters  of  digital  controllers,  like  internal  reference  generation  or  controller  dynamics,  can  be  easily  set  and  optimized  with  the  Atos 

Z-SW  programming  software,  available  in  three  different  versions  according  to  the  driver’s  communication  interface:  Z-SW-PS  (Serial),  Z-SW-BC

(CANopen) and Z-SW-BP (PROFIBUS DP).

A proper connection is required between the PC and the electronic controller communication port: for a more detailed description of software interface,

PC requirements, adapters, cables and terminators, please refer to technical table 

G500

.

Digital controllers with fieldbus communication interface (-BC and -BP) can be managed in real-time by the machine control unit; it is required to imple-

ment in the machine control the standard communication as described in the user manuals supplied with the relevant programming software; please con-

tact Atos technical office for assistance.

Programming software, must be ordered separately:

Z-SW-*

(mandatory - first supply) = Dvd including Z-SW-* software installer and operator manuals; it allows the registration to Atos digital service

Z-SW-*-N

(optional - next supplies)  = as above but not including the registration form for Atos digitals service

On first supply of the Z-SW-* software, it is required to apply for the registration in the Atos download area: www.download.atos.com .

Once the registration is completed, the password will be sent by email.

The software remains active for 10 days from the installation date and then it stops until the user inputs his password.

With the password it is also possible to download the latest releases of the Atos software, manuals, drivers and configuration files.

USB Adapters, Cables and Terminators, can be ordered separately (see tab. G500)

13

MAIN SOFTWARE PARAMETER SETTINGS

11.14 Digital input signals (DI1 - DI8)

The 8 digital inputs can be used to trigger a command or to read a system state. For each input by the Z-SW software, it is possible to set the polarity and

to match a proper condition within the following:

- start/stop/switch-over command in case of internal reference generation (see 3.2)

- specific operative command for hydraulic axis mode (referencing mode, jog mode, automatic mode)

- jog command

- disable pressure / force alternated control

11.15 Digital output signals (DO1 - DO7)

The 7 digital outputs can be used to generate digital signals useful to the system synchronization and for monitoring purpose. The digital outputs can be

configured in polarity and all the channels can be independently programmed by the Z-SW software.

Typically the digital outputs are used to:

- set alarm condition related with the hydraulic axis working phase

- identify a particular working condition to synchronize other machine functionalities

- signal target position reached

- signal pressure / force control active

- signal tracking error

11.16 CANopen communication signals (only for /BC option)

For controllers with CANopen communication interface (only for /BC option), the connections are located on the rear connector: pin f28 (CAN_GND), pin

f30 (CAN_L) and pin f32 (CAN_H).

G340

For a detailed descriptions of the available settings, wirings and installation procedures, please refer to the programming manual Z-MAN-ME-KZ included

in the Z-SW-* Dvd programming software (see section 

).

13.1 External reference and transducer parameters

Allow to configure the controller reference and transducer inputs, analog or digital, to match the specific application requirements:

Scaling parameters

define the correspondence of these signals with the specific actuator stroke or force to be controlled

Limit parameters 

define maximum/minimum stroke and force to detect possible alarm conditions

Homing parameters

define the startup procedure to initialize incremental transducer (e.g. encoder)

13.2 Position PID control dynamics parameters

Allow to optimize and adapt the position controller closed loop to the wide range of hydraulic system characteristics:

PID (position)

each  part  of  the  position  controller  closed  loop  algorithm  (proportional,  fine  positioning  advanced  integral,  derivative,  feed

forward, etc.) can be modified in order to match the application requirements.

13.3 Multiple pressure/force PID control dynamics parameters

Allow to optimize and adapt the pressure/force controller closed loop to the wide range of hydraulic system characteristics:

PID (pressure/force)

each  part  of  the  pressure/force  controller  closed  loop  algorithm  (proportional,  integral,  derivative,  feed  forward,  etc)  can  be

modified in order to match the application requirements. Through Atos software or using dedicated digital inputs it is possible

to  select  up  to  four  different  pressure/force  PID  parameters  setting,  stored  into  the  controller.  Switching  the  active  setting  of

pressure/force  PID  during  the  machine  cycle  allows  to  optimize  the  system  dynamic  response  in  different  hydraulic  working

conditions (volume, flow, etc.).

13.4 Control output signal parameters

Allow to configure the controller command for the proportional valve which regulates the hydraulic flow to the actuator:

Scaling parameters

define the correspondence of the command signal to the specific valve reference signal range

Limit parameters 

define maximum/minimum range to detect possible alarm conditions

13.5 Monitoring parameters

Allow to configure the controller monitoring function of the positioning error (difference between actual reference and feedback) and detects anomalous

conditions:

Monitoring parameters

maximum allowed errors can be set for both static and dynamic positioning phases, and dedicated waiting times can be set to

delay the activation of the alarm condition and relevant reaction (see 13.6)

13.6 Fault parameters

Allow to configure how the controller detect and react to alarm conditions:

Diagnostics parameters

define different conditions, threshold and delay time to detect alarm conditions

Reaction parameters

define  different  actions  to  be  performed  in  case  of  alarm  presence  (stop  at  actual  or  preprogrammed  position,  emergency

forward/backward, controller disabling, etc.)

13.7 Digital IO configuration

Allow to configure the controller’s digital inputs/outputs to trigger/generate signals from /for the external machine central unit:

- Polarity

define the signal active state

- Trigger condition

define the input state to run a predefined internal command (see 11.14)

- Output state

define the digital output based on the internal controller state (see 11.15)

13.8 Motion phases parameters

When the internal reference generation is active a pre-programmed cycle can be generated; start/stop/switch-over commands and reference generation

types parameters can be set to design a customized sequence of motion phases adapted to the specific application requirements (see 3.2).

12

Содержание atos E-BM-AC Series

Страница 1: ......

Страница 2: ...ection degree electronic filters on input and output lines CE marking grating the conformity to the EMC Directive Electromagnetic compatibility Applications Pressure flow position open or closed loop systems according to the block diagram 2 E MI E MI electronic driver plug format as per DIN 43650 AC for proportional valve without transducer 01F for single solenoid proportional valve Options standa...

Страница 3: ...er is designed to receive a voltage reference signal according to the following options potentiometers mounted externally and wired according to the application diagrams external reference signals generated by PLC see voltage from 0 to 10V current from 0 to 20 mA only with option RR 4 3 Monitor signal This voltage output signal allows to measure the current supplied to the coil read by a voltmeter...

Страница 4: ...rk with signal from 0 to 10 V The current supplied to the coil can be measured by a voltmeter connected between pins M and 2 of the screw terminal The reading range will be l mA 10xV mV for example reading 70 mV the current in the coil will be 7001mA Bias adjustment dead band compensation see Supply electrical power to the driver supply a reference signal voltage 0 1 VDC Gradually turn the P4 bias...

Страница 5: ...ic connections shown in this technical table The device must be verified on the machine because the magnetic field may be different from the test conditions SAFETY The electrical signals for example reference signals feedback and enable signal of electronic drivers must not be used to realize safety condi tions of the machine This is in accordance with the provisions of european directives Safety ...

Страница 6: ...ransducer 01F for single solenoid proportional valves 011F for two single solenoid proportional valves 05F for double solenoid proportional valves Notes the reference R2 must be supplied only for E BM AC 011F with the version 011F it is possible to regulate two single solenoid proportional valves also contemporary Options standard symmetrical ramp RR with adjustable dissymmetrical ramps Series num...

Страница 7: ...ning differential hydraulic operations Bias dead band Regulation of dead band adjusts the hydraulic zero of the valve starting position adjustment to a minimum signal of 200 mV The electronic card is factory pre set for the valve it is coupled with according to the set code see section 4 4 E BM AC 05F driver for double solenoid are equip ped with an internal channel selector enabling the relevant ...

Страница 8: ... R2 0 2 VDC by the potentiometer P2 For E BM AC 05F supply a reference voltage R1 0 2 VDC turn clockwise the potentiometer P1 for solenoid S1 until the movement of the controlled actua tor is obtained turn the potentiometer P1 in the opposite direction until the actuator is stopped repeat the operation and supply a reference signal voltage R1 0 2 VDC by the potentiometer P2 Scale adjustment see Su...

Страница 9: ...mpatibility of electronic drivers is valid only for wirings realized according to the typical electric connections shown in this technical table The device must be verified on the machine because the magnetic field may be different from the test conditions SAFETY The electrical signals for example reference signals feedback and enable signal of electronic drivers must not be used to realize safety...

Страница 10: ...ent to the solenoid of Atos proportional valves without pressure or position transdu cer regulating the spool position the flow or the pressure according to the electronic reference signal Features bias and scale regulations by poten tiometers symmetrical standard or dissym metrical RR and RR 4 options rising and falling ramp generator factory pre setted Eurocard format DIN 41494 modular unit 4 in...

Страница 11: ...e reference inversion signal on contact 18c 5 24 VDC 4 3 Monitor signal This voltage output signal allows to measure the current supplied to the coil read by a voltmeter on the front panel test points see Reading scale is 1 mV 1 mA To visualize the signals use voltmeters with impedance 10 KΩ 4 4 Set code Basic calibration of the electronic driver is factory preset according to the proportional val...

Страница 12: ...abling signal usually 24VDC It could be useful in emergency conditions to inhibit the driver by zeroing this signal Bias adjustment Dead band compensation see Supply a reference signal voltage 0VDC for E ME AC 01F and 0 1VDC for E ME AC 05F Gradually turn bias potentiometer s until a movement of the controlled actuator is obtained Turn in the opposite direction until the actuator is stopped Scale ...

Страница 13: ...EAD BAND SCALE CURRENT AMPLIF E PROTECTIVE EARTH TE NOISELESS EARTH C ALTERNATIVE BONDING TO NOISELESS EARTH TERMINAL CURRENT AMPLIF ELETTROMAGNETIC COMPATIBILITY Atos electronic drivers and proportional valves are designed according to the 2004 108 CE Directive Electromagnetic Compatibility and according to EN 50081 2 Emission and EN 50082 2 Immunity standards The electromagnetic compatibility of...

Страница 14: ...ucer s feedback Features bias regulation scale and dissymmetrical ramps regulation voltage standard or current I option reference signal voltage standard or current C option feedback signal test point for reference and feedback control on front panel factory pre setted Eurocard format DIN 41494 plug in unit electronic filters on input and output lines CE marking granting the conformity to the EMC ...

Страница 15: ... VDC or disable 0 V the driver without swit ching off the power supply use this signal to cyclically inhibit the driver or in emergency condi tions 4 4 Set code Basic calibration of the electronic driver is factory preset according to the proportional valve it has to be coupled with These pre calibrations are identified by a standard number in the model code as follows For ex proof valves insert a...

Страница 16: ...e Ramps see If the card is being used in a open loop system push the switch from position ramp off standard to position ramp on see B Calibrate the ramp settings only if dynamic impacts and tenden cies towards instability persist after optimizations of the whole system Adjust the ramp settings using the ramp potentiometers P3 and P4 until the phenomenon has been eliminated Clockwise rotation incre...

Страница 17: ... for wirings realized according to the typical electric connections shown in this technical table The device must be verified on the machine because the magnetic field may be different from the test conditions SAFETY The electrical signals for example reference signals feedback and enable signal of electronic drivers must not be used to realize safety condi tions of the machine This is in accordan...

Страница 18: ...pen or closed loop regulation systems according to the block diagram 2 2 BLOCK DIAGRAM G150 USER FUNCTIONS AND CONTROL OPTIONS USER INTERFACE SUPPLY 24V REFERENCE SIGNALS ENABLE SIGNALS SPOOL FEEDBACK SPOOL FEEDBACK SOLENOID SUPPLY OUTPUT INPUTS DEAD BAND ADJUST SPOOLS POSITION CONTROL RAMP GENERATOR OUTPUT PROTECTION FEEDBACK FAULT SENSE ELECTRONIC DRIVER E ME L 01H E ME E ME electronic driver in...

Страница 19: ...er to the noiseless earth terminal TE 4 2 Reference signal The electronic driver is designed to receive external voltage or current reference signals accord ing to Note that drivers suitable to receive current reference option I have signal values in the range 4 to 20mA For single solenoid valves with two external positions 60 the reference signal is sym metrical 10 V 5 V 4 3 Enabling signal The d...

Страница 20: ...4 until the phenomenon has been eliminated Clockwise rota tion increase in ramp time 11 10 7 8 7 7 7 10 9 7 10 9 8 8 8 E ME L 01H TOPOGRAPHICAL VIEW OF REGULATIONS 7 RAMPS AND SETTINGS 9 E ME L 01H DIAGRAM DISSYMMETRICAL RISING AND FALLING RAMPS GENERATOR P3 P4 P3 P4 A B C SCALE SWITCH RAMP SWITCH POS 2 0 5 5 V POS 1 0 10 10V STD SETTING RAMP ON RAMP OFF STD SETTING Power on led green Fail safe le...

Страница 21: ...ealized according to the typical electric connections shown in this technical table The device must be verified on the machine because the magnetic field may be different from the test conditions SAFETY The electrical signals for example reference signals feedback and enable signal of electronic drivers must not be used to realize safety condi tions of the machine This is in accordance with the pr...

Страница 22: ... RP Electronic driver in sealed box AC for proportional valves without transducer 01F for single solenoid proportional valves 05F for double solenoid proportional valves Options standard symmetrical ramp RR with adjustable dissymmetrical ramps RRE with external ramp setting I suitable to receive current reference signal 4 20 mA Series number Set code see 4 4 AC 01F 1 MODEL CODE G100 USER FUNCTIONS...

Страница 23: ...the noiseless earth terminal TE The driver is designed to correc tly work with 24 VDC 20 or 12 VDC 20 nominal voltage sup ply coupled with coils having a resistance from 2 0 Ω to 13 4 Ω as shown in the side table 4 2 Reference signal The electronic driver is designed to receive voltage or current reference signals see table Note that drivers suitable to receive current reference option I have sign...

Страница 24: ...mpensation see Supply a reference signal voltage 0VDC for E RP AC 01F and 0 1 VDC for E RP AC 05F Gradually turn bias potentiometer s until a movement of the controlled actuator is obtained Turn in the opposite direction until the actuator is stopped Scale adjustment see Supply max reference signal voltage for E RP AC 05F driver repeat for max negative voltage in the specificated range and turn sc...

Страница 25: ...tions SAFETY The electrical signals for example reference signals feedback and enable signal of electronic drivers must not be used to realize safety condi tions of the machine This is in accordance with the provisions of european directives Safety requirements of fluid technology systems and com ponents hydraulics EN 982 Special attention must be payed to switch on switch off of electronic driver...

Страница 26: ...entation CE mark according to EMC directive Software Features Setting of valve s functional parame ters bias scale ramps dither Linearization function for the hydraulic regulation 2 selectable modes for electronic refe rence signal external analog input or internal generation Max power limitation W option Selectable range of electronic referen ce analog input voltage or current I option Complete d...

Страница 27: ...wer supply to drive standard proportional valves 3 2 W solenoid IMAX 3 3 A with 12 VDC power supply to drive proportional valves with 6 option 2 1 W solenoid Reference input signal CMD1 see 4 2 Standard voltage Input range 0 10 VDC Input impedance Ri 50 kW I option current Input range 4 20 mA 0 20 mA Input impedance Ri 500 W Enble Input Signal CMD2 see 4 5 ON OFF Input Signal CMD1 CMD2 see 4 6 Inp...

Страница 28: ...can be set in a range from 80 to 500 Hz default value is 200Hz Lower dither setting reduces the hysteresis but also reduces the regulation stability In some appli cation this can lead to vibration and noise right setting usually depends on system setup Default dither is a valid setting for a wide range of hydraulic applications 6 5 Linearization Linearization function allows to set the relation be...

Страница 29: ...nable input signal is used to select which driver solenoid has to be active To operate double solenoid valves it is required to parallel wire the two drivers see following scheme select opposite polarity default and reverse for the two enable signals see 4 5 manage from PLC or machine unit 1 analog reference signal corresponding to desired valve s regulation and 1 ON OFF signal to select the activ...

Страница 30: ... dither Linearization function for the hydraulic regulation 2 selectable modes for electronic refe rence signal external analog input or internal generation Max power limitation W option Selectable range of electronic referen ce analog inputs voltage or current Complete diagnostics of driver status solenoid and driver fault conditions Intuitive graphic interface E BM A 01H Electronic driver in DIN...

Страница 31: ...meters directly connected to the driver using the 5 VDC supply output available at pin C3 and C4 4 5 Enable Input Signal pin D3 referred to pin D2 Enable input signal allows to enable disable the current supply to the solenoids without removing the electrical power supply to the driver it is used to maintain active the serial connection and the other driver functions when the valve must be disable...

Страница 32: ...dither is a valid setting for a wide range of hydraulic applications 6 5 Linearization Linearization function allows to set the relation between the reference input signal and the current supplied to the solenoid Linearization is useful for applications where it is required to linearize the valve s regulation in a defi ned working condition e g maximum pressure control at defined working flow 6 6 ...

Страница 33: ...NABLE Enable 24 VDC or disable 0 VDC the driver see 4 5 Input on off signal D4 STATUS Fault default or software selected output see 4 6 Output on off signal Note Only for double or two single solenoid driver version 05H 8 FRONT PANNEL CONNECTOR AND LEDS RJ45 CONNECTOR PIN SIGNAL DESCRIPTION 1 Not connected 2 Not connected 3 Not connected 4 GND Signal zero data line 5 RX Driver receiving data line ...

Страница 34: ... the proportional valve which regulates the hydraulic flow to the actuator The position feedback interfaces are SSI incremental encoder potentiometer or stan dard analog inputs voltage or current software selectable A front panel serial port is always present for configuration and monitoring of the controller The controller can be operated in real time by external or internally generated reference...

Страница 35: ...1 I2 I3 I4 I5 I6 I7 I8 A1 A2 X1 X2 OK DWN UP ENT ESC RS232 PROFIBUS DRIVER T A B P T M L Z ME KZ O1 O2 O3 O4 O5 O6 O7 A3 A4 A5 I1 I2 I3 I4 I5 I6 I7 I8 A1 A2 X1 X2 OK DWN UP ENT ESC RS232 PROFIBUS DRIVER T A B P T M P P Z ME KZ O1 O2 O3 O4 O5 O6 O7 A3 A4 A5 I1 I2 I3 I4 I5 I6 I7 I8 A1 A2 X1 X2 OK DWN UP ENT ESC RS232 PROFIBUS one remote pressure transducer has to be installed on the actuator s port ...

Страница 36: ...ydraulic electronic system architecture thanks to internal reference generation for repetitive working cycles SSI digital position transducer for accurate axis control two pressure transducers for alternated force control auxiliary digital inputs output to synchronize the machine functions fieldbus connection for machine remote control and advanced diagnostics DRIVER T A B P T Z ME KZ O1 O2 O3 O4 ...

Страница 37: ...fferent transducer interfaces are available on the controller depending to the system requirements potentiometer analog signal SSI and encoder see 7 3 Transducers with digital interface SSI and encoder allow the user to get high resolution and accurate measures Transducers with analog interface potentiometer and analog signal grant simple and cost effective solutions 7 2 Pressure force transducers...

Страница 38: ...ring are not allowed via front panel operations 8 2 LED indication The led indications are used to display the internal status Active OK of the con troller or the status of the digital IO of the Z ME KZ There are 22 led divided in four different types internal controller s status Active OK digital input status I1 I8 digital output status O1 O7 software programmable led A1 A5 for specific functions...

Страница 39: ...stics to select the transducer type that mach the specific application requirements see 7 2 The input range and polarity are software selectable within the maximum range 10 VDC for voltage or 0 20 mA for current default setting is 0 10 VDC 11 6 Analog valve monitor input signal VALVE_MONITOR VALVE_MONITOR The controller allows to monitor the regulation of the proportional valve which operates the ...

Страница 40: ...ction 13 1 External reference and transducer parameters Allow to configure the controller reference and transducer inputs analog or digital to match the specific application requirements Scaling parameters define the correspondence of these signals with the specific actuator stroke or force to be controlled Limit parameters define maximum minimum stroke and force to detect possible alarm condition...

Страница 41: ...LVE REF VALVE MONITOR VALVE MONITOR DI 1 DI 3 DI 2 VREF 10VDC VREF 10VDC P_TR P_TR AGND DO 1 DO 2 1 1 For the valve driver electrical connection please refer to the specific technical table 2 For the potentiometer position transducer connection please refer to transducer datasheet 3 For the analog position transducer connection please refer to transducer datasheet 1 For the valve driver electrical...

Страница 42: ......

Отзывы: