MCS 1000 Series
Error analysis / remedy
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 56 / 76
BeWa MCS1000 3435427f V130 en-us 2012-06-15.doc
2012-06-15
Error analysis / remedy
Using several supply voltages makes it necessary to define the following terms for
error analysis:
Designation
Description
Operation voltage
Voltage for operating the MCS (electronics, coil system).
Measurement
voltage
Voltage U
M1/2
at switching output 1/2 for superordinate
controllers.
Signal value
Measurement voltage on = high
Measurement voltage off = low
Remove the connection cable on the MCS for error analysis and check the socket
on the connection cable according to the following steps:
Step
Pin <-> Pin Description
1
1
<-> 3
Check the operation voltage.
2
2
<-> 4
Check the measurement voltage U
M1
at the switching
output 1
3
8
<-> 4
Check the measurement voltage U
M2
at the switching
output 2