Performing Maintenance
OXiStop OXS
en
Page 75 / 108
MoWa OXS 3992763e en-us 2018-08-10.docx
2018-08-10
Checking/setting the electronic pressure switch (EDS)
Before the unit is started up, and every time the electronic pressure switch
EDS has been replaced, check the settings in accordance with the following
specifications.
Check or configure the electronic pressure sensor EDS with the following
alarm settings:
Alarm 1:
Error MOX
(when a pressure higher than 1200 mbar is
reached over a period of 99.99 s)
-
->
1200
mbar
-
->
15
mbar
Alarm 2:
Free air in the tank
(when a pressure higher than 450 mbar is
reached over a period of 25 s)
-
->
450
mbar
-
->
15
mbar