Performing maintenance / inspection
FAM 15-70 ATEX
en
Page 75 /
88
BEWA FAM-15-70 II 2G IIB+H2 T4 EX02 4510066 en-us 2020-01-24.docx
2020-01-24
Maintenance
interval
Description
Before startup
Check the level and the color of the oil (see Vacuum
Pump Operating Instructions)
Daily
Check the level and the color of the oil (see Vacuum
Pump Operating Instructions)
Visually inspect the entire unit for leaks.
Weekly
Check the level and the color of the oil (see Vacuum
Pump Operating Instructions)
Check that the oil fill plug [f] is firmly tightened. Max.
torque 35 Nm.
Check the vacuum pump for oil leaks
– in case of leaks,
immediately remove the vacuum pump from service
and have it repaired.
Monthly
Make sure that the unit and individual components are
free of dust and dirt, clean if necessary.
Every 6 Months
Also clean the fan cowlings, fan wheels, the ventilation
grilles and cooling fins.
Check inspection and control measurement of the
electrical connection [i] of the electric motor of the
vacuum pump.
Circumferential backlash and visual inspection of the
coupling [h] (see operating manual/maintenance
schedule of the vacuum pump)
Replace intake air filter / dehumidifier.
Every six months
or every 1500
operating hours
Change the oil (see Vacuum pump Operating
Instructions)
Removal of the detonation flame arrester [e] on the
vacuum pump for maintenance according to
maintenance schedule (see Vacuum Pump Operating
Instructions).
All deposits, such as dirt and dust, threaten the explosion safety of
the unit.