Performing maintenance / inspection
FAM 15-70 ATEX
en
Page 70 /
88
BEWA FAM-15-70 II 2G IIB+H2 T4 EX02 4510066 en-us 2020-01-24.docx
2020-01-24
10
.
Place the element locking cap on the upper
filter element (1).
Turn the locking cap 90° in the clockwise
direction to lock it in place.
No element locking cap = no filtration.
11
.
Put the intermediate piece (b) on the lower
section (c).
Mount the lower housing tensioning clamp (1)
and tighten it with a torque of 20 Nm. Secure
using the lock nut.
Put the cover (a) on the intermediate piece
(b).
Mount the upper housing tensioning clamp (2)
and tighten it with a torque of 20 Nm. Secure
using the lock nut.
We recommend applying lubricant
containing a slip additive to the threads of the
housing tensioning clamp each time filters are
changed so that it remains easy to remove.
Lubricant containing a slip additive
– HYDAC
p/no. 3066287
12
.
Open all shut-off valves on the FAM (inlet and
outlet).
Switch on the FAM at the main switch.