E
E
33
32
D/E/F 18.303
.H5/05.19
D/E/F 18.303
.H5/05.19
11. Error messages
if an error is detected, then a corresponding error message appears which
must be acknowledged by pressing any key. Possible error messages are
as follows:
ER.01
the switching points and hystereses/switch-back points are not within
the permissible setting range.
action:
correct the settings.
ER.10
a data error has been detected in the saved settings. Possible causes
are strong electromagnetic interference or a component fault.
action:
check all the settings (programming enable, switching points, switch-
back points and basic settings) and correct these if necessary. if the
error occurs frequently, please contact hydac service.
ER.12
an error has been detected in the stored calibration data.
Possible causes are strong electromagnetic interference or a
component fault.
action:
after acknowledging the error, the unit will continue to operate, with
reduced accuracy, until it is switched off. however, check all important
settings (switching points, switch-back points and basic settings) and
correct these if necessary. the unit must in any case be returned to
the manufacturer for re-calibration or repair.
– – – –
an error has been detected in the stored calibration data. Possible
causes are strong electromagnetic interference or a component fault.
action:
check the supply voltage to the Ets 1700
9.2. altErinG thE hardWarE ProGraMMinG EnablE
disconnect the unit from the supply voltage.
remove the 4 screws from the unit front panel (figure 1).
lift front panel off carefully and put to one side.
Push slide switch on the lower board to the required position (figure 2):
"
OFF
": programming disabled.
replace front panel on the unit and screw into position, ensuring that the
front panel seal is in the correct position.
figure 1
figure 2
10. altering the mounting position
disconnect the unit from the supply voltage.
remove the 4 screws from the front plate of the unit (figure 1).
carefully lift off the front panel and turn through 180°.
replace the front panel on the unit and screw into position, ensuring that the
front panel seal is in the correct position (figure 2).
figure 1
figure 2
sensor connection
sensor connection
programming
possible
disable