Input(s) AutoPush config section
Sets the behaviour of AutoPush for DI inputs. During activation, the sending of information about
changes in the input state to the portal is accelerated. The function can be enabled individually
for each input.
Sensor(s) AutoPush config
Sets the behaviour of the AutoPush function for individual sensors. The function accelerates the
sending of information about fluctuating values to the portal. When the measured sensor value
changes since last communication with the portal by more than the defined value, the device
connects to the portal again and sends the new value.
Portal Debug Log section
For debugging only. Event co Debug window for sending data to the portal.
•
Push Period
– Period of sending data to the remote portal. The period is determined by the portal
and cannot be changed by the user.
•
Log Period
– Period of storing data for the portal in the cache. The period is determined by the
portal and cannot be changed by the user.
•
Current Push Timer
– Timer indicating the time remaining until sending data to the portal.
•
Current Log Timer
– Timer indicating the time remaining until saving the data for the portal in
the cache.
•
AutoPush Block Timer
– Time of incidents for AutoPush. If the permitted number of incidents for
one Push period is exceeded, the AutoPush function will be blocked.
•
Retransmit number
– Counts the number of invalid Push attempts.
•
Manual Push
– Button for instant sending of data to the portal.
What is AutoPush
•
AutoPush
– By default, the device thermometer sends data to the portal at a fixed interval
defined by the relevant portal (in the case of the SensDesk portal, once every 15 minutes)
and the user cannot change this value. A special case is the start and end of Alarms, when
extraordinary sending will occur. AutoPush serves for the extraordinary sending of values also
whenever the sensor value changes by more than the defined AutoPush value.
This concerns only the setting of communication between the device and the online portal. The
values of local alarms are set in the portal.