background image

5

Considering δ=90°, Φ is equivalent to the dielectric loss angle, so it is very simple to evaluate

MOA with Φ; Φ is 81°

to

86° if there is no interphase interference. According to the requirement

that the resistive current cannot exceed 25% of the total current, Φ cannot be less than 75.5°. refer

to the following table for the segmented evaluation of MOA performance:

Φ

<75°

75°~77

°

78°~80° 81°~83° 84°~88°

>89°

Performance Very poor

Poor

Average

Good

Excellent With interference

In fact, consider in case of Φ<80°

Figure 8 Projection Method

Figure 9 Interphase Interference of In-line Arresters

2.2

Interphase Interference

In the field measurement, the intermediate B phase of the in-line arresters impacts the

leakage currents A and C through the stray capacitance: A phase φ is reduced by 2° or so and the

resistive current is increased; C phase φ is reduced by 2° or so and the resistive current is reduced

to the negative; B phase is not changed. This phenomenon is called interphase interference (Figure

9).

2.3

Performance Evaluation of MOA with Interference

1. It is suggested that the same phase PT secondary voltage should be used to measure the

same phase MOA current. The compensation angle is 0, and the interphase interference is not

considered in the measurement. For the laboratory measurement, the compensation angle (Φ0=0)

should not be used.

The interphase interference can be considered when MOA performance is evaluated. Based on

B phase Φ, the reduced value of A phase Φ is basically equal to the increased value of C phase Φ

according to the symmetry of interphase interference, so as to evaluate the interphase

interference angle. For example, if A phase Φ is 2° less than the normal value, and C phase Φ is 3°

more than the normal value, the interphase interference will be approximately 2.5°. When MOA

performance is evaluated, A is +2.5°, B phase Φ is not changed, and C phase Φ is 2.5°.

2. If the interphase interference is considered in the measurement, the compensation angle

can be set for A/C phase and is added to Φ. Considering the interphase interference of B phase to

A/C phase is symmetrical, if the angle Φca for the leading Ia of Ic is measured, A/C phase will be

respectively compensated, the same phase PT secondary voltage will be used to measure the same

phase MOA current, and the above compensation angle will be added. MOA performance will be

evaluated directly according to Φ.

VII. Precautions:

1. When measure the reference voltage from PT or the measuring end of the testing

transformer, carefully check wiring to avoid the PT secondary or test voltage short circuit.

2. Be careful not to wrongly connect the current and voltage sampling lines in the connecting

process.

3. In the laboratory experiment, the high voltage power supply cannot use the series excitation

testing transformer.

A phase B phase

C phase

Stray

capacitance

With

interference

With

interference

Without

interference

Without

interference

Содержание HTYB-3H

Страница 1: ...u can find the changes in the appendix Sorry for the inconvenience If you have further questions welcome to contact with our service department The input output terminals and the test column may bring...

Страница 2: ...this product can only be used within the prescribed scope Only qualified technician can carry out maintenance or repair work To avoid fire and personal injury Use Proper Power Cord Only use the power...

Страница 3: ...o not operate this product when covers or panels removed Use Proper Fuse Only use the fuse with type and rating specified for the product Avoid Touching Bare Circuit and Charged Metal Do not touch the...

Страница 4: ...ecurity Terms Warning indicates that death or severe personal injury may result if proper precautions are not taken Caution indicates that property damage may result if proper precautions are not take...

Страница 5: ...able of Contents I Overview 1 II Structure Diagram for Instrument Panel 1 III Main Technical Indexes 1 IV Wiring Diagrams 1 V Instrument Operation 2 VI Measurement Principle and Data Analysis 4 VII Pr...

Страница 6: ...ests II Structure Diagram for Instrument Panel Figure 1 III Main Technical Indexes Range of reference voltage input peak 10V 200V Customizable 0 250V Measurement range of full leakage current peak 100...

Страница 7: ...r and the ground Boosting value 10KV 1 5 35KV 3 2 Online wiring diagram live test Figure 3 In the online measurement the voltage signal input is connected to the secondary side of PT located at the sa...

Страница 8: ...inding For example for the testing transformer with AC output rated voltage of 50KV the rated voltage of the measuring instrument winding is usually 100V so the transformation ratio is 50KV 100V 500 D...

Страница 9: ...s fund I 0 000mA Freq 50 00Hz Res I3 0 000mA A Power 0 000W Res I5 0 000mA R Power 0 000W Res I7 0 000mA Ratio 0 000 Res IMax 0 000mA Angle 0 000 Diff Phase 0 00 Prev Next Y Print N Esc Figure 7 Data...

Страница 10: ...rference can be considered when MOA performance is evaluated Based on B phase the reduced value of A phase is basically equal to the increased value of C phase according to the symmetry of interphase...

Страница 11: ...t To judge whether the valve disc of the metal oxide arrester is aged or affected with damp usually observe the change of resistive leakage current flowing through the zinc oxide valve disc in the nor...

Страница 12: ...7 you understand the change to the resistive leakage current of the metal oxide arrester you can predict whether the above failures occur...

Отзывы: