Arrester characteristics tester

System Settings

Data Measurement

Data View

Instrument Calibration

Time Calibration

↑↓

Move

Y

Enter

N

Esc

Figure 4 Main Menu

2. Click System Settings to display the menu as shown in Figure 5:

Arrester characteristics tester

Compensation Angle +0.000

Transformation Ratio 01000

Device No

0000-A

↑↓

Move

Y

Enter

N

Esc

Figure 5 System Settings Menu

In this menu, you can set the transformation ratio and the compensation angle.

The entry of digits is - 1 2 3 4 5 6 7 8 9 0. Cycle.

The transformation ratio cannot be

negative, the first digit of the compensation angle is only -, and other entry is wrong. One

decimal point is only used between the data.

↑: cycle the digit. ↓: move to the right. After the digits are entered, press Return to save.

* Note the correct algorithm of the transformation ratio:

Determination method for transformation ratio of testing transformer: the transformation

ratio herein should be turns ratio or voltage ratio of high voltage winding and measuring

instrument winding. For example, for the testing transformer with AC output rated voltage of

50KV, the rated voltage of the measuring instrument winding is usually 100V, so the

transformation ratio is 50KV/100V=500. Determination method for online transformation ratio:

for example, the transformation ratio of 110KV arrester is (110KV/

)/(100KV/

)=1100.

*Algorithm of input compensation angle:

When the compensation angle is 0, firstly measure the angle φ{φA and φC} for phase A and

phase C, and use {φC-φA}/2=compensation angle, wherein φA is positive, and φC is negative.

3. Click the menu “Data Measurement” to display the menu as shown in Figure 6:

Figure 6 Data Test Main Menu

Compensation angle: for the stored data, the compensation angle can be modified, but the

modified value only influences the currently displayed/printed data and cannot be saved.

Transformation ratio: PT or transformation ratio of testing transformation, the displayed test

0000-A

Arrester Test Interface

Full V

0.000KV

Full I

0.000mA

Fund V

0.000KV

Res I

0.000mA

Cap I

0.000mA Res Fund I

0.000mA

Freq

50.00Hz

Res I3

0.000mA

A Power

0.000W

Res I5

0.000mA

R Power

0.000W

Res I7

0.000mA

Ratio

0.000

Res IMax

0.000mA

Angle

0.000

Diff Phase

0.00

Wave

Save

Print

Esc

3

3

Содержание HTYB-3H

Страница 1: ...u can find the changes in the appendix Sorry for the inconvenience If you have further questions welcome to contact with our service department The input output terminals and the test column may bring...

Страница 2: ...this product can only be used within the prescribed scope Only qualified technician can carry out maintenance or repair work To avoid fire and personal injury Use Proper Power Cord Only use the power...

Страница 3: ...o not operate this product when covers or panels removed Use Proper Fuse Only use the fuse with type and rating specified for the product Avoid Touching Bare Circuit and Charged Metal Do not touch the...

Страница 4: ...ecurity Terms Warning indicates that death or severe personal injury may result if proper precautions are not taken Caution indicates that property damage may result if proper precautions are not take...

Страница 5: ...able of Contents I Overview 1 II Structure Diagram for Instrument Panel 1 III Main Technical Indexes 1 IV Wiring Diagrams 1 V Instrument Operation 2 VI Measurement Principle and Data Analysis 4 VII Pr...

Страница 6: ...ests II Structure Diagram for Instrument Panel Figure 1 III Main Technical Indexes Range of reference voltage input peak 10V 200V Customizable 0 250V Measurement range of full leakage current peak 100...

Страница 7: ...r and the ground Boosting value 10KV 1 5 35KV 3 2 Online wiring diagram live test Figure 3 In the online measurement the voltage signal input is connected to the secondary side of PT located at the sa...

Страница 8: ...inding For example for the testing transformer with AC output rated voltage of 50KV the rated voltage of the measuring instrument winding is usually 100V so the transformation ratio is 50KV 100V 500 D...

Страница 9: ...s fund I 0 000mA Freq 50 00Hz Res I3 0 000mA A Power 0 000W Res I5 0 000mA R Power 0 000W Res I7 0 000mA Ratio 0 000 Res IMax 0 000mA Angle 0 000 Diff Phase 0 00 Prev Next Y Print N Esc Figure 7 Data...

Страница 10: ...rference can be considered when MOA performance is evaluated Based on B phase the reduced value of A phase is basically equal to the increased value of C phase according to the symmetry of interphase...

Страница 11: ...t To judge whether the valve disc of the metal oxide arrester is aged or affected with damp usually observe the change of resistive leakage current flowing through the zinc oxide valve disc in the nor...

Страница 12: ...7 you understand the change to the resistive leakage current of the metal oxide arrester you can predict whether the above failures occur...

Отзывы: