AK-CC 210
Digital inputs
There are two digital inputs both of which can be used for the
following functions:
- Case cleaning
- Door contact function with alarm
- Starting a defrost
- Coordinated defrost
- Change-over between two temperature reference
- Retransmission of a contact’s position via data communication
Case cleaning function
This function makes it easy to steer the refrigeration appliance
through a cleaning phase. Via three pushes on a switch you
change from one phase to the next phase.
The first push stops the refrigeration – the fans keep working
”Later”: The next push stops the fans
”Still later”: The next push restarts refrigeration
The different situations can be followed on the display.
On the network a cleaning alarm is transmitted to the system unit.
This alarm can be ”logged” so that proof of the sequence of events
is provided.
Door contact function
In cold rooms and frost rooms the door switch can switch the light
on and off, start and stop the refrigeration and give alarm if the
door has remained open for too long.
Defrost
Depending on the application you may choose between the fol-
lowing defrost methods:
Natural:
Here the fans are kept operating during the defrost
Electric:
The heating element is activated
Brine:
The valve is kept open so that the brine can flow
through the evaporator
Hotgas:
Here the solenoid valves are controlled so that the
hotgas can flow through the evaporator
Start of defrost
A defrost can be started in different ways
Interval:
Defrost is started at fixed time intervals, say, every
eighth hour
Refrigeration time:
Defrost is started at fixed refrigeration time inter-
vals, in other words, a low need for
refrigeration will ”postpone” the coming defrost
Schedule:
Here defrost can be started at fixed times of the
day and night. However, max. 6 times
Contact:
Defrost is started with a contact signal on a digital
input
Network:
The signal for defrost is received from a system unit
via the data communication
S5 temp
In 1:1 systems the efficiency of the evaporator can
be followed. Icing-up will start a defrost.
Manual:
An extra defrost can be activated from the control-
ler’s lower-most button. (Though not for
application 4).
All the mentioned methods can be used at random – if just one
them is activated a defrost will be started.
-
+
+
°C
1
÷
+
Fan
2
÷
÷
Off
3
+
+
°C
Hot gas application
Содержание CHINO TY3
Страница 6: ...6 Cut and Plan Views ...
Страница 8: ...8 Spec Sheet ...
Страница 9: ...9 01 01 ...
Страница 10: ...10 0 1 0 0 1 1 1 2 0 1 ...
Страница 11: ...11 0 1 0 23 43 5 0 1 0 23 43 5 5 5 1 6 1 1 7 23 43 ...
Страница 12: ...12 0 1 23 23 1 23 23 1 0 1 4 5 0 4 6 0 4 4 4 ...
Страница 42: ...42 Controller for temperature control AK CC 210 User Guide ADAP KOOL Refrigeration control systems ...