50
AK-CC 210
Manual RS8EP502 © Danfoss 12-2015
9
Activation of reference displacement
When the function is changed to ON the thermostat reference will be displaced by
the value in r40. A
ctivation can also take place via input DI1 or DI2 (defined in o02 or
o37).
r39
Th. offset
Value of reference displacement
The thermostat reference and the alarm values are shifted the following number of
degrees when the displacement is activated. Activation can take place via r39 or input
DI
r40
Th. offset K
Night setbck
(start of night signal)
Forced cool.
(start of forced cooling)
Alarm
Alarm settings
The controller can give alarm in different situations. When there is an alarm all the
ligh
t-emitting diodes (LED) will flash on the controller front panel, and the alarm relay
will cut in.
With data communication the impor-
tance of the individual alarms can be
defined. Setting is carried out in the
“Alarm destinations” menu.
Alarm delay
(short alarm delay)
If one of the two limit values is exceeded, a timer function will commence. The alarm
will not become active until the set time delay has been passed. The time delay is set
in minutes.
A03
Alarm delay
Time delay for door alarm
The time delay is set in minutes.
The function is defined in o02 or in o37.
A04
DoorOpen del
Time delay for cooling
(long alarm delay)
This time delay is used during start-up, during defrost, immediately after a defrost.
There will be change-over to the normal time delay (A03) when the temperature has
dropped below the set upper alarm limit.
The time delay is set in minutes.
A12
Pulldown del
Upper alarm limit
Here you set when the alarm for high temperature is to start. The limit value is set in
°C (absolute value). The limit value will be raised during night operation. The value is
the same as the one set for night setback, but will only be raised if the value is posi-
tive.
The limit value will also be raised in connection with reference displacement r39.
A13
HighLim Air
Lower alarm limit
Here you set when the alarm for low temperature is to start. The limit value is set in °C
(absolute value).
The limit value will also be raised in connection with reference displacement r39.
A14
LowLim Air
Delay of a DI1 alarm
A cut-out/cut-in input will result in alarm when the time delay has been passed. The
function is defined in o02.
A27
AI.Delay DI1
Delay of a DI2 alarm
A cut-out/cut-in input will result in alarm when the time delay has been passed. The
function is defined in o37
A28
AI.Delay DI2
Signal to the alarm thermostat
Here you have to define the ratio between the sensors which the alarm thermostat
has to use. S3, S4 or a combination of the two.
With setting 0% only S3 is used. With 100% only S4 is used
A36
Alarm S4%
Reset alarm
EKC error
Compressor
Compressor control
The compressor relay works in conjunction with the thermostat. When the thermo-
stat calls for refrigeration will the compressor relay be operated.
Running times
To prevent irregular operation, values can be set for the time the compressor is to run
once it has been started. And for how long it at least has to be stopped.
The running times are not observed when defrosts start.
Min. ON-time (in minutes)
c01
Min. On time
Min. OFF-time (in minutes)
c02
Min. Off time
Содержание CHINO TY3
Страница 6: ...6 Cut and Plan Views ...
Страница 8: ...8 Spec Sheet ...
Страница 9: ...9 01 01 ...
Страница 10: ...10 0 1 0 0 1 1 1 2 0 1 ...
Страница 11: ...11 0 1 0 23 43 5 0 1 0 23 43 5 5 5 1 6 1 1 7 23 43 ...
Страница 12: ...12 0 1 23 23 1 23 23 1 0 1 4 5 0 4 6 0 4 4 4 ...
Страница 42: ...42 Controller for temperature control AK CC 210 User Guide ADAP KOOL Refrigeration control systems ...