ElectroVap RTH
Tank Maintenance
(Continued)
Maintenance
Lift the tank cover (note the positioning
mark) and lay it upside down on the top of
the humidifier (Picture 7). Remove the high
water level tank and lay it on the top of the
humidifier.
Adjust the collection bag on the tank rim
and attach the handles to the tank lateral
hooks (picture 8).
Release the tank holding steel cord and
swing the tank down : the mineral deposit
falls into the flexible container. (Picture 9).
Remove the collection bag and swing the
tank back to intermediate position. Attach
the holding steel cord to the tank. (Picture
7)
Grease the square tank gasket with
silicone grease.
TAKE CARE : the tank gasket must be
changed if found flawed. Cut used
gasket with a knife or cutter ; clean out
the tank rim with acetone and secure
the new gasket with heat resistant glue
(320°F) appropriate to steel material.
Put the tank cover back onto the tank
body taking care to align the positioning
mark and put back the high water level
tank cap. Swing the tank up (Picture 10).
Then tighten up the black knob and
reconnect the drain and steam hoses.
The humidifier is now ready for operation.
(Picture 11)
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
26