ElectroVap RTH
Steam Pipe Positioning
Installation
Install the distribution pipe on the duct with 4
scews.
A minimum distance of 12 in. between the
center of the steam distribution pipe and the
top of the duct should be alllowed. Where
the distribution pipe is installed at an angle
of between 30° and 45°, this may be
reduced to 6 in.
Where the application requires two
distribution pipes, the above-mentioned
recommendations should be observed
keeping a minimum space of 6 in. between
the pipes.
(d) is the minimum distance between the
distribution pipe and any obstacle within the
duct (see table on page 12).
Where a steam pipe is installed after a bend,
it should be positioned in the main air flow.
In vertical ducts where the air flow is upward
or downwards, the steam distribution pipe
should be mounted at an angle of 15° from
vertical
6 in.
12 in.