Hubbell Diesel Engine Fire Pump Controller LX3000 Скачать руководство пользователя страница 7

Table 6-1  Troubleshooting

Condition

Possible cause

Checks

Action

Batteries

Voltmeters should read
at least 12.5 or 25 VDC
Check each battery in
bank for correct voltage

Check electrolyte

Test and recharge bad
   battery(s)
Replace battery(s) with
   good battery(s)

Check battery and
ground connections

Check battery voltage

Check battery cables
and connections

Clean and tighten
   connections as
   necessary

Engine does not crank
with MANUAL
START

Battery circuits

Check engine starter
cables and connections

Clean and tighten
   connections as
   necessary

Engine does not crank
using MANUAL
START - Battery No. 1

MANUAL CRANK #1
switch

Check battery voltage
while holding
MANUAL CRANK #1
switch

Refer to schematic
Use volt/ohm meter to
   determine which
   component is faulty

Engine does not crank
using MANUAL
START - Battery No. 2

MANUAL CRANK #2
switch

Check battery voltage
while holding
MANUAL CRANK #2
switch

Refer to schematic
Use volt/ohm meter to
   determine which
   component is faulty

If voltage checks indicate batteries and circuits OK then the engine starter or the pilot (or starting)
contactors are faulty.

Содержание Diesel Engine Fire Pump Controller LX3000

Страница 1: ...Controls Inc A subsidiary of Hubbell Incorporated 4301 Cheyenne Dr Archdale NC 27263 Telephone 336 434 2800 FAX 336 434 2803 Instruction Manual Model LX3000 Diesel Engine Fire Pump Controller Publicat...

Страница 2: ...if allowed by local jurisdiction to TB1 14 and battery common Start Up Instructions 1 Adjust the pressure switch set points to meet water system requirements The adjustment switches are located on the...

Страница 3: ...time be brought consecutively into the display for revision or checking Revisions are carried out by writing over the existing programs using the steps outlined above 5 Set Control Settings also see a...

Страница 4: ...in the AUTO position disconnect the battery wire on TB1 6 The BATTERY NO 1 FAILURE LED should come on within two minutes The alarm should sound and the Common TROUBLE relay should energize Reconnect t...

Страница 5: ...Start a With the AUTOMATIC MANUAL SWITCH in the AUTO position open the remote start contacts TB1 12 13 starting the engine b Turn the CONTROLLER ON OFF SWITCH to the OFF position to stop engine c Clos...

Страница 6: ...hock or accident hazard Before troubleshooting perform the following checks a visual inspection for physical damage b ensure that all switches are in the normal operating position c ensure that the en...

Страница 7: ...circuits Check engine starter cables and connections Clean and tighten connections as necessary Engine does not crank using MANUAL START Battery No 1 MANUAL CRANK 1 switch Check battery voltage while...

Страница 8: ...n signal absent Magnetic Pickup or circuit faulty Check Crank 1 and Crank 2 relays on Engine Relay Board Check Run LED on Main Logic Board Check for Pickup signal at Main Logic Board Replace Engine Re...

Страница 9: ...to solenoid drain valve or faulty valve Faulty Timer Check Water Dump Solenoid Relay Check solenoid valve Check Timer program Replace Engine Relay Board Replace valve Replace Timer Alarm does not soun...

Страница 10: ...ed magnetic sensor Main Logic Board faulty Check sensor installation Replace sensor Replace Main Logic Board Cranking and rest periods greater than or less than 15 2 sec Engine cranks less than six ti...

Страница 11: ...r loss Power Sense Board or Main Logic Board faulty Check Power Sense Board Check Main Logic Board Replace Power Sense Board Replace Main Logic Board Engine does not stop with optional AUTO STOP Anoth...

Страница 12: ......

Страница 13: ...the left side of the chart plate Re attach the chart hub knob and screw securely by hand against the chart Press the change chart button 3 again for approximately one 1 second until the pen begins to...

Страница 14: ...Figure 4 Pressure Settings Start Pressure Stop Pressure 3 Status LED S SEE NOTE...

Страница 15: ...d WARNING Lead acid batteries generate explosive gases during normal operation Precautions Do not work alone Wear eye protection and protective clothing Have soap and water available in case of skin c...

Страница 16: ...ing Chart Continued Symptom Possible cause Solution Charging LED blinking Battery voltage high due to Engine charging circuit supplying charging voltage above control charger value Troubleshoot engine...

Страница 17: ...Location and Description of Control Settings...

Отзывы: