c.

 

Turn the AUTOMATIC / MANUAL SWITCH to the AUTO position to stop the engine.

Automatic Engine Cranking in TEST

a.

 

Disconnect engine wire from TB1-1 to prevent starting.

b.

 

Press the TEST PUSHBUTTON on the weekly TEST TIMER.  The solenoid valve opens to discharge
water, and the pressure switch contacts close to initiate cranking.

c.

 

The controller will crank the engine on battery 1 for 15 second intervals followed by 15 second rest period.
It will then crank 15 seconds on battery 2, followed by 15 second rest period. This cycle is repeated 3
times, then cranking should will stop and the FAILURE TO START light comes on, the alarm sounds, and
the Common TROUBLE relay is energized.

d.

 

Turn the CONTROLLER ON / OFF to the OFF position.

e.

 

Reconnect the starter motor cable(s).

Automatic Pressure Start

a.

 

With the AUTOMATIC / MANUAL SWITCH in the AUTO position, lower the system pressure below the
Start pressure.

b.

 

The engine will start and run until pressure is above the Stop setting and the STOP button is pressed, or the
CONTROLLER ON / OFF SWITCH is turned to the OFF position, or the optional Automatic Stop Timer,
typically set for 15 or 30 minutes, stops the engine.

Battery Failure Test

a.

 

With the AUTOMATIC / MANUAL SWITCH in the AUTO position, disconnect the battery wire on

TB1-6. The BATTERY NO.1 FAILURE LED should come on within two minutes. The alarm should
sound and the Common TROUBLE relay should energize. Reconnect the wire to TB1-6. Reset the alarm
by turning the CONTROLLER ON / OFF - RESET SWITCH from CONTROLLER ON to OFF - RESET
position then back to the CONTROLLER ON position.

b.

 

Disconnect the battery wire on TB1-8. The BATTERY NO.2 FAILURE LED should come on within two
minutes. The alarm should sound and the Common TROUBLE relay should energize. Reconnect the wire
to TB1-8. Reset the alarm by turning the CONTROLLER ON / OFF - RESET SWITCH from
CONTROLLER ON to OFF - RESET position then back to the CONTROLLER ON position.

Charger Failure Test

a

 

With the AUTOMATIC / MANUAL SWITCH in the AUTO position, disconnect the wire on TB1-6, and
disconnect the AC input to charger(s) no. 1. BATTERY NO.1 FAILURE & CHARGER 1 FAILURE light
should come on within two minutes. The alarm should sound and the Common TROUBLE relay should
energize. Reconnect the wire to TB1-6, reset the alarm by turning the CONTROLLER ON / OFF - RESET
SWITCH from CONTROLLER ON to OFF - RESET position then back to the CONTROLLER ON
position.

b

 

Repeat the above for battery No. 2 & charger(s) no. 2, using the wire on TB1-8

Low Oil Pressure Test

a.

 

With the AUTOMATIC / MANUAL SWITCH in the AUTOMATIC position, start the engine by
depressing the TEST PUSHBUTTON on the Weekly Timer.

Содержание Diesel Engine Fire Pump Controller LX3000

Страница 1: ...Controls Inc A subsidiary of Hubbell Incorporated 4301 Cheyenne Dr Archdale NC 27263 Telephone 336 434 2800 FAX 336 434 2803 Instruction Manual Model LX3000 Diesel Engine Fire Pump Controller Publicat...

Страница 2: ...if allowed by local jurisdiction to TB1 14 and battery common Start Up Instructions 1 Adjust the pressure switch set points to meet water system requirements The adjustment switches are located on the...

Страница 3: ...time be brought consecutively into the display for revision or checking Revisions are carried out by writing over the existing programs using the steps outlined above 5 Set Control Settings also see a...

Страница 4: ...in the AUTO position disconnect the battery wire on TB1 6 The BATTERY NO 1 FAILURE LED should come on within two minutes The alarm should sound and the Common TROUBLE relay should energize Reconnect t...

Страница 5: ...Start a With the AUTOMATIC MANUAL SWITCH in the AUTO position open the remote start contacts TB1 12 13 starting the engine b Turn the CONTROLLER ON OFF SWITCH to the OFF position to stop engine c Clos...

Страница 6: ...hock or accident hazard Before troubleshooting perform the following checks a visual inspection for physical damage b ensure that all switches are in the normal operating position c ensure that the en...

Страница 7: ...circuits Check engine starter cables and connections Clean and tighten connections as necessary Engine does not crank using MANUAL START Battery No 1 MANUAL CRANK 1 switch Check battery voltage while...

Страница 8: ...n signal absent Magnetic Pickup or circuit faulty Check Crank 1 and Crank 2 relays on Engine Relay Board Check Run LED on Main Logic Board Check for Pickup signal at Main Logic Board Replace Engine Re...

Страница 9: ...to solenoid drain valve or faulty valve Faulty Timer Check Water Dump Solenoid Relay Check solenoid valve Check Timer program Replace Engine Relay Board Replace valve Replace Timer Alarm does not soun...

Страница 10: ...ed magnetic sensor Main Logic Board faulty Check sensor installation Replace sensor Replace Main Logic Board Cranking and rest periods greater than or less than 15 2 sec Engine cranks less than six ti...

Страница 11: ...r loss Power Sense Board or Main Logic Board faulty Check Power Sense Board Check Main Logic Board Replace Power Sense Board Replace Main Logic Board Engine does not stop with optional AUTO STOP Anoth...

Страница 12: ......

Страница 13: ...the left side of the chart plate Re attach the chart hub knob and screw securely by hand against the chart Press the change chart button 3 again for approximately one 1 second until the pen begins to...

Страница 14: ...Figure 4 Pressure Settings Start Pressure Stop Pressure 3 Status LED S SEE NOTE...

Страница 15: ...d WARNING Lead acid batteries generate explosive gases during normal operation Precautions Do not work alone Wear eye protection and protective clothing Have soap and water available in case of skin c...

Страница 16: ...ing Chart Continued Symptom Possible cause Solution Charging LED blinking Battery voltage high due to Engine charging circuit supplying charging voltage above control charger value Troubleshoot engine...

Страница 17: ...Location and Description of Control Settings...

Отзывы: