Hubbell Diesel Engine Fire Pump Controller LX3000 Скачать руководство пользователя страница 3

2)

 

Press and hold the 

Ÿ

 clock symbol key during entire time setting procedure.

a)

 

Press the 

Day 

key to bring the actual day of the week into display.

b)

 

Press the 

h

 button to set the hours and the 

m

 button to set the minutes. If the keys are depressed for

more than a second, the digits will advance rapidly.

c)

 

Release the 

Ÿ

 clock key when finished with the settings. The colon between the hours and minutes will

be flashing indicating the timer has started.

Programming

1)

 

To set the Timer to start the engine once a week and run for a selected period of time.

Press 

Timer 

once (do not keep depressed) The display will show “1ON and “--:--“for the time.

a)

 

Press 

h+  m+ 

to set the ON time.

b)

 

Press 

Day

 to select the day of the week to run.

c)

 

Press 

Timer 

key to enter program. The display will show 1”OFF”.

d)

 

Program OFF command using steps b-d above.

e)

 

Press the 

Ÿ

 key to return to time od day display.

2)

 

To review the programming

a)

 

Press 

Timer 

key to review the individual commands as preprogrammed, at any time, be brought

consecutively into the display for revision or checking. Revisions are carried out by writing over the
existing programs using the steps outlined above.

5.

 

Set Control Settings – 

also see attached drawing for locations of items 5 through 11.

a.

 

Set the pressure switch start time delay (P/SWT DELAY SEC) on the Main Logic Board. The
adjustment range is 0 to 15 seconds in 1 second increments.

b.

 

Set the AC Power Loss Delay Time on the Main Logic Board. The adjustment range is 0 to 90
seconds in 6 second increments.

c.

 

Set the Auto Stop time switch (SW6). Settings are none, 15 minutes or 30 minutes.

d.

 

Set the AC PowerLoss Start switch (SW4–2). Setting is on or off.

e.

 

Set the AC Loss Audible Alarm switch (SW4-1). Setting is on or off.

6.

 

Controller Testing

a.

 

Verify pressure is above the Stop setting.

b.

 

Turn CONTROLLER ON / OFF SWITCH to the ON position

Check the Test Timer to make sure that the Timer contacts are not about to close.

  Closure of the Timer

contacts during testing causes incorrect results.

Manual Start

a.

 

Turn the AUTOMATIC / MANUAL SWITCH to the MANUAL position.

b.

 

Operate the MANUAL CRANK # 1 switch or the MANUAL CRANK # 2 switch. Release as soon as the
engine starts.

Содержание Diesel Engine Fire Pump Controller LX3000

Страница 1: ...Controls Inc A subsidiary of Hubbell Incorporated 4301 Cheyenne Dr Archdale NC 27263 Telephone 336 434 2800 FAX 336 434 2803 Instruction Manual Model LX3000 Diesel Engine Fire Pump Controller Publicat...

Страница 2: ...if allowed by local jurisdiction to TB1 14 and battery common Start Up Instructions 1 Adjust the pressure switch set points to meet water system requirements The adjustment switches are located on the...

Страница 3: ...time be brought consecutively into the display for revision or checking Revisions are carried out by writing over the existing programs using the steps outlined above 5 Set Control Settings also see a...

Страница 4: ...in the AUTO position disconnect the battery wire on TB1 6 The BATTERY NO 1 FAILURE LED should come on within two minutes The alarm should sound and the Common TROUBLE relay should energize Reconnect t...

Страница 5: ...Start a With the AUTOMATIC MANUAL SWITCH in the AUTO position open the remote start contacts TB1 12 13 starting the engine b Turn the CONTROLLER ON OFF SWITCH to the OFF position to stop engine c Clos...

Страница 6: ...hock or accident hazard Before troubleshooting perform the following checks a visual inspection for physical damage b ensure that all switches are in the normal operating position c ensure that the en...

Страница 7: ...circuits Check engine starter cables and connections Clean and tighten connections as necessary Engine does not crank using MANUAL START Battery No 1 MANUAL CRANK 1 switch Check battery voltage while...

Страница 8: ...n signal absent Magnetic Pickup or circuit faulty Check Crank 1 and Crank 2 relays on Engine Relay Board Check Run LED on Main Logic Board Check for Pickup signal at Main Logic Board Replace Engine Re...

Страница 9: ...to solenoid drain valve or faulty valve Faulty Timer Check Water Dump Solenoid Relay Check solenoid valve Check Timer program Replace Engine Relay Board Replace valve Replace Timer Alarm does not soun...

Страница 10: ...ed magnetic sensor Main Logic Board faulty Check sensor installation Replace sensor Replace Main Logic Board Cranking and rest periods greater than or less than 15 2 sec Engine cranks less than six ti...

Страница 11: ...r loss Power Sense Board or Main Logic Board faulty Check Power Sense Board Check Main Logic Board Replace Power Sense Board Replace Main Logic Board Engine does not stop with optional AUTO STOP Anoth...

Страница 12: ......

Страница 13: ...the left side of the chart plate Re attach the chart hub knob and screw securely by hand against the chart Press the change chart button 3 again for approximately one 1 second until the pen begins to...

Страница 14: ...Figure 4 Pressure Settings Start Pressure Stop Pressure 3 Status LED S SEE NOTE...

Страница 15: ...d WARNING Lead acid batteries generate explosive gases during normal operation Precautions Do not work alone Wear eye protection and protective clothing Have soap and water available in case of skin c...

Страница 16: ...ing Chart Continued Symptom Possible cause Solution Charging LED blinking Battery voltage high due to Engine charging circuit supplying charging voltage above control charger value Troubleshoot engine...

Страница 17: ...Location and Description of Control Settings...