Hubbell Diesel Engine Fire Pump Controller LX3000 Скачать руководство пользователя страница 10

No HIGH ENGINE
TEMP indication

Water temperature
switch

Connect a jumper
across the water
temperature switch on
the engine
Start engine with
MANUAL START
switch
Verify that engine starts
and alarm sounds

Replace water
temperature switch

Engine overspeed does
not stop engine
No indication

Indication but engine
does not stop under
overspeed simulation

Faulty or mis-adjusted
magnetic sensor

Main Logic Board
faulty

Check sensor
installation

Replace sensor

Replace Main Logic
Board

Cranking and rest
periods greater than or
less than 15 

±

 2 sec.

Engine cranks less than
six times

Engine continues to
crank in AUTO
position but does not
start

Main Logic Board
faulty

Check Main Logic
Board

Replace Main Logic
Board

Controller does not
crank engine with good
battery

Engine cranking and
indication OK

Engine Relay Board
faulty

Main Logic Board
faulty

Check Engine Relay
Board

Check Main Logic
Board

Replace Engine Relay
Board

Replace Main Logic
Board

Содержание Diesel Engine Fire Pump Controller LX3000

Страница 1: ...Controls Inc A subsidiary of Hubbell Incorporated 4301 Cheyenne Dr Archdale NC 27263 Telephone 336 434 2800 FAX 336 434 2803 Instruction Manual Model LX3000 Diesel Engine Fire Pump Controller Publicat...

Страница 2: ...if allowed by local jurisdiction to TB1 14 and battery common Start Up Instructions 1 Adjust the pressure switch set points to meet water system requirements The adjustment switches are located on the...

Страница 3: ...time be brought consecutively into the display for revision or checking Revisions are carried out by writing over the existing programs using the steps outlined above 5 Set Control Settings also see a...

Страница 4: ...in the AUTO position disconnect the battery wire on TB1 6 The BATTERY NO 1 FAILURE LED should come on within two minutes The alarm should sound and the Common TROUBLE relay should energize Reconnect t...

Страница 5: ...Start a With the AUTOMATIC MANUAL SWITCH in the AUTO position open the remote start contacts TB1 12 13 starting the engine b Turn the CONTROLLER ON OFF SWITCH to the OFF position to stop engine c Clos...

Страница 6: ...hock or accident hazard Before troubleshooting perform the following checks a visual inspection for physical damage b ensure that all switches are in the normal operating position c ensure that the en...

Страница 7: ...circuits Check engine starter cables and connections Clean and tighten connections as necessary Engine does not crank using MANUAL START Battery No 1 MANUAL CRANK 1 switch Check battery voltage while...

Страница 8: ...n signal absent Magnetic Pickup or circuit faulty Check Crank 1 and Crank 2 relays on Engine Relay Board Check Run LED on Main Logic Board Check for Pickup signal at Main Logic Board Replace Engine Re...

Страница 9: ...to solenoid drain valve or faulty valve Faulty Timer Check Water Dump Solenoid Relay Check solenoid valve Check Timer program Replace Engine Relay Board Replace valve Replace Timer Alarm does not soun...

Страница 10: ...ed magnetic sensor Main Logic Board faulty Check sensor installation Replace sensor Replace Main Logic Board Cranking and rest periods greater than or less than 15 2 sec Engine cranks less than six ti...

Страница 11: ...r loss Power Sense Board or Main Logic Board faulty Check Power Sense Board Check Main Logic Board Replace Power Sense Board Replace Main Logic Board Engine does not stop with optional AUTO STOP Anoth...

Страница 12: ......

Страница 13: ...the left side of the chart plate Re attach the chart hub knob and screw securely by hand against the chart Press the change chart button 3 again for approximately one 1 second until the pen begins to...

Страница 14: ...Figure 4 Pressure Settings Start Pressure Stop Pressure 3 Status LED S SEE NOTE...

Страница 15: ...d WARNING Lead acid batteries generate explosive gases during normal operation Precautions Do not work alone Wear eye protection and protective clothing Have soap and water available in case of skin c...

Страница 16: ...ing Chart Continued Symptom Possible cause Solution Charging LED blinking Battery voltage high due to Engine charging circuit supplying charging voltage above control charger value Troubleshoot engine...

Страница 17: ...Location and Description of Control Settings...

Отзывы: