Hubbell Diesel Engine Fire Pump Controller LX3000 Скачать руководство пользователя страница 13

Pressure Switch / Recorder
Changing the Chart Paper

First, locate the “change chart” button (#3) located in the upper left
corner of the recorder. Press and hold this button for approximately one
(1) second until the pen begins to move to the left of the chart. Wait
until the pen has moved completely off of the chart.  To remove the
chart paper, unscrew (counter-clockwise) the “hub” knob at the center
of the chart.  Remove the old chart paper and position the new one so
that the correct time coincides with the time line groove on the chart
plate.  Refer to Figure 3 for the location of the time line groove on the
left side of the chart plate. Re-attach the chart “hub” knob and screw securely (by hand) against the chart.
Press the “change chart” button (#3) again for approximately one (1) second until the pen begins to move back
onto the chart paper.

Pen replacement

Slide the used pen cartridge off the pen arm.  Slide on new cartridge and remove tip cover.

To replace the pen, loosen the two screws that hold
the pen arm and the pen cartridge, and metal pen arm
be removed as an assembly.  Refer to Figure 3 for
the location of the pen arm screws.  Unsnap the
plastic “U” clip tab of the pen cartridge from the
metal pen arm (see Figure 2), remove and discard the
old pen cartridge.  Replace the new cartridge by
opening the hinge and snapping it securely around
the metal pen arm.

Figure 3 - RECORDER ASSEMBLY

Figure 2

Figure 1

Содержание Diesel Engine Fire Pump Controller LX3000

Страница 1: ...Controls Inc A subsidiary of Hubbell Incorporated 4301 Cheyenne Dr Archdale NC 27263 Telephone 336 434 2800 FAX 336 434 2803 Instruction Manual Model LX3000 Diesel Engine Fire Pump Controller Publicat...

Страница 2: ...if allowed by local jurisdiction to TB1 14 and battery common Start Up Instructions 1 Adjust the pressure switch set points to meet water system requirements The adjustment switches are located on the...

Страница 3: ...time be brought consecutively into the display for revision or checking Revisions are carried out by writing over the existing programs using the steps outlined above 5 Set Control Settings also see a...

Страница 4: ...in the AUTO position disconnect the battery wire on TB1 6 The BATTERY NO 1 FAILURE LED should come on within two minutes The alarm should sound and the Common TROUBLE relay should energize Reconnect t...

Страница 5: ...Start a With the AUTOMATIC MANUAL SWITCH in the AUTO position open the remote start contacts TB1 12 13 starting the engine b Turn the CONTROLLER ON OFF SWITCH to the OFF position to stop engine c Clos...

Страница 6: ...hock or accident hazard Before troubleshooting perform the following checks a visual inspection for physical damage b ensure that all switches are in the normal operating position c ensure that the en...

Страница 7: ...circuits Check engine starter cables and connections Clean and tighten connections as necessary Engine does not crank using MANUAL START Battery No 1 MANUAL CRANK 1 switch Check battery voltage while...

Страница 8: ...n signal absent Magnetic Pickup or circuit faulty Check Crank 1 and Crank 2 relays on Engine Relay Board Check Run LED on Main Logic Board Check for Pickup signal at Main Logic Board Replace Engine Re...

Страница 9: ...to solenoid drain valve or faulty valve Faulty Timer Check Water Dump Solenoid Relay Check solenoid valve Check Timer program Replace Engine Relay Board Replace valve Replace Timer Alarm does not soun...

Страница 10: ...ed magnetic sensor Main Logic Board faulty Check sensor installation Replace sensor Replace Main Logic Board Cranking and rest periods greater than or less than 15 2 sec Engine cranks less than six ti...

Страница 11: ...r loss Power Sense Board or Main Logic Board faulty Check Power Sense Board Check Main Logic Board Replace Power Sense Board Replace Main Logic Board Engine does not stop with optional AUTO STOP Anoth...

Страница 12: ......

Страница 13: ...the left side of the chart plate Re attach the chart hub knob and screw securely by hand against the chart Press the change chart button 3 again for approximately one 1 second until the pen begins to...

Страница 14: ...Figure 4 Pressure Settings Start Pressure Stop Pressure 3 Status LED S SEE NOTE...

Страница 15: ...d WARNING Lead acid batteries generate explosive gases during normal operation Precautions Do not work alone Wear eye protection and protective clothing Have soap and water available in case of skin c...

Страница 16: ...ing Chart Continued Symptom Possible cause Solution Charging LED blinking Battery voltage high due to Engine charging circuit supplying charging voltage above control charger value Troubleshoot engine...

Страница 17: ...Location and Description of Control Settings...

Отзывы: