Installation Drawings

Dual-LIte

®

 TRX

 MBC

14

Figure 7

Control wiring diagram, Dual-Lite TRX MBC, three breakers, with interlock

NOTES:
1. Customer furnished electrode conductor to be installed in accordance

with national and local electrical codes. 

2. See installation manual for additional connection information. 
3. Overcurrent protection is based on 80% rated devices. 
4. MBB auxiliary switch connections are on the normally closed and common positions. 
5. MIB auxiliary switch connections are on the normally opened and common positions. 
6. MBC when connected to UPS module, all control and power wiring is supplied by Dual-LIte.

If the MBC is remote from the UPS module, the cables between the MBC and UPS module
must be supplied by others. 

7. Optional SKRU and associated wiring (703, 704, 706). 
8. Shown is typical for a four-breaker configuration. Also available: a two-breaker configuration

(MIB, MBB) and a three-breaker configuration (BIB, MIB, MBB). 

MBB See Note 6

Customer Feed

Output
Neutral

AC
Output

Kirk

Key K2

Kirk

Key K1

MIB

See Note 7

From
Utility

Output
Ground

Ground to
Unit Frame

Ground to
Unit Frame

Optional
See Note 9

Input Neutral 

See Note 1

SKRU - Solenoid Key Release Unit
KO-Key Operator

Main Ground Busbar

Field-Supplied Wiring

Inner Door

Factory-Supplied Wiring

ØA
ØB
ØC

ØA
ØB
ØC

ØA
ØB
ØC

SKRU

RIB

BIB

W04
W05
W06

W87

W86

W85

W90

W89

W88

W08
W09

TB1

Fuses, 2

Lamp

AC 120V

704

710

Push
Button

K0

UPS

Fuse

AC Output

AC Input

Aux

702

2A

A

B

C

A

B

C

mN

PE

X9J24

MFP_O 1

MFP_S 3

MFP_C 5

Main_abnl_O 2

Main_abnl_S 4

Main_abnl_C 6

X9J23

BFP_O 1

BFP_S 3

BFP_C 5

INV_O 2

INV_S 4

INV_C 6

X9J26

GND_Dry 15

Q5_Status 13

GND_Dry 11

Q5_Status 9

Wiring shown for a four-breaker system. 
Refer to Note 8 for three-breaker 
configurations.

Detail A

DETAIL A

Содержание Dual-Lite TRX MBC

Страница 1: ...Dual Lite TRX MBC User Manual 10 30kVA 60Hz...

Страница 2: ......

Страница 3: ...orque Requirements 19 FIGURES Figure 1 Cabinet arrangement Dual Lite TRX UPS battery cabinets maintenance bypass cabinet 7 Figure 2 One line diagram single input three breaker Dual Lite TRX MBC 10 30k...

Страница 4: ...13 Table 6 Dual Lite TRX MBC specifications 16 Table 7 Dimensions for Dual Lite TRX UPS with Dual Lite TRX MBC 16 Table 8 Additional weight for Dual Lite TRX 10 30kVA UPS with internal batteries 17 T...

Страница 5: ...heck for voltage with both AC and DC voltmeters prior to making contact AVERTISSEMENT Le centre de gravit lev des appareils pr sente un risque de renversement lors des d placements pouvant entra ner d...

Страница 6: ...NT Risque d arc ou de d charge lectrique pouvant entra ner des dommages mat riels des blessures et m me la mort Les pr cautions de s curit habituelles suffisent lorsque le syst me est en mode de fonct...

Страница 7: ...diately Verify that the correct equipment is being installed The equipment supplied has an identification tag on the back of the main door reporting the type size and main calibration parameters of th...

Страница 8: ...capable of supporting its weight for instance check that doorways lifts ramps etc are adequate and that there are no impassable corners or changes in the level of corridors Ensure that the cabinet wei...

Страница 9: ...ent is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading 1 5 Cable Entry Cables can enter the Dual Lite TRX MBC from the bottom...

Страница 10: ...rounding conductor should be sized according to local or NEC codes cable lengths type of protection etc The grounding cable connecting the UPS to the main ground system must follow the most direct rou...

Страница 11: ...ps attached to the UPS The 600mm maintenance bypass cabinet ships separately from the UPS Dual Lite TRX UPS Dual Lite TRX UPS Dual Lite TRX UPS Maintenance Bypass Cabinet Matching Battery Cabinet Matc...

Страница 12: ...o follow adequate grounding procedures can result in electric shock hazard to personnel and the risk of fire should a ground fault occur AVERTISSEMENT Risque de d charge lectrique pouvant entra ner de...

Страница 13: ...e X9 J23 and J26 Tighten the connections to the proper torque see Table 14 8 Replace the panels Notes Refer to the Dual Lite TRX UPS installation manual SL 25648 for additional details about the Dual...

Страница 14: ...and bypass must share the same single source 3 A neutral is required from the system AC input source A full capacity neutral conductor is recommended Grounding conductors are recommended 4 Bypass and...

Страница 15: ...VA system Dual Lite TRX MBC Breaker Configuration Configured Breaker 3 BIB MBB MIB Table 3 Terminal block details 200mm Dual Lite TRX MBC three breakers 10 30kVA system Terminal Block Single Input Sys...

Страница 16: ...Top and bottom cable entry available through removable access plates Remove punch to suit conduit size and replace 5 Unit bottom is structurally adequate for forklift handling 6 Control wiring and pow...

Страница 17: ...0kVA system Terminal Block Single Input System TB2 Input TB3 Output NOTES 1 All dimensions are in inches mm 2 Control wiring and power wiring must be run in separate conduits 3 All wiring is to be in...

Страница 18: ...ng 703 704 706 8 Shown is typical for a four breaker configuration Also available a two breaker configuration MIB MBB and a three breaker configuration BIB MIB MBB MBB See Note 6 Customer Feed Output...

Страница 19: ...stallation Drawings 15 Dual LIte TRX MBC Figure 8 Solenoid key release unit 200mm Dual Lite TRX MBC K0 K1 K2 TB1 Fuseblock for SKRU Solenoid key release unit is mounted between the BIB and MBB breaker...

Страница 20: ...ree of Protection for UPS Enclosure IP 20 with and without front door open Standards and Conformities UL1778 5th Edition CSA 22 2 107 3 14 ISTA Procedure 1H WEEE Minimum Clearance Top in mm 24 610 Min...

Страница 21: ...ut Bypass and AC output Recommended cable sizes are suitable for operation at a maximum temperature of 104 F 40 C Table 10 Dual Lite TRX MBC input currents single input main Voltage 3 Ph 60 Hz MBC Rat...

Страница 22: ...kcmil 54179 60160 350kcmil 256 30695 112 400kcmil 256 30695 1403 500kcmil 256 30695 339 Table 13 Recommended lug sizes Compression Type M12 1 2 bolt Cable Size T B Copper Two Hole T B Aluminum Two Hol...

Страница 23: ...e these values unless the equipment is labeled otherwise Table 14 Busbar torque for power wiring Bolt Shaft Size Torque Lb in Nm 3 8 M10 192 22 1 2 M12 428 48 Table 15 Terminal block torque with compr...

Страница 24: ...DL 25652_REV0_02 16 Dual Lite TRX MBC User Manual 10 30kVA 60Hz...

Отзывы: