Mechanical Installation

Dual-LIte

®

 TRX

 MBC

4

1.3

Environmental Considerations

1.3.1

Room

The Dual-Lite TRX MBC is intended for indoor installation and should be located in a cool, dry, clean-

air environment with adequate ventilation to keep the ambient temperature within the specified 

operating range (see 

3.0 - Specifications

).

All models of the Dual-Lite TRX MBC are convection-cooled. To permit air to enter and exit and 

prevent overheating or malfunctioning, do not cover the ventilation openings.
When bottom entry is used, the conduit plate can be removed and punched and replaced. The bottom 

conduit plate must be replaced for proper airflow. If necessary to cool the room, install a system of 

room extractor fans.

1.3.2

Storage

Should the equipment not be installed immediately, it must be stored in a room for protection against 

excessive humidity and or heat sources (see 

Table 6

).

1.4

Positioning

The cabinet is structurally designed to handle lifting from the base.
Access to the power terminals, auxiliary terminals blocks and power switches is from the top and 

sides.
The top and side removable panels are secured to the chassis by screws. The side panel can be 

removed for access to the power connections bars, auxiliary terminal blocks and power isolators.

1.4.1

Moving the Cabinets

The route to be travelled between the point of arrival and the unit’s position must be planned to make 

sure that all passages are wide enough for the unit and that floors are capable of supporting its 

weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no 

impassable corners or changes in the level of corridors).
Ensure that the cabinet weight is within the designated surface weight loading (kg/cm

2

) of any 

handling equipment. See 

Table 8

 for the weight of the Dual-Lite TRX MBC 200mm, 300mm, 600mm, 

and 800mm models

Tables 7

 through

9

 provide detailed dimension and weight information for the 

Dual-Lite TRX UPS and Dual-Lite TRX MBC when they are bolted together and shipped as a system.
Ensure that any lifting equipment used in moving the cabinet has sufficient lifting capacity.
The Dual-Lite TRX MBC can be handled by means of a fork lift or similar equipment. For operations 

with a fork lift, refer to installation drawings in 

2.0 - Installation Drawings

.

Because the weight distribution in the cabinet is uneven, use extreme care during handling and 

transporting.
When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree 

tilt with the forklift.
Handling the unit with straps is not authorized.

NOTE

The Dual-Lite TRX MBC is suitable for mounting only on concrete and other noncombustible 

surfaces.

!

WARNING

Risk of moving heavy units and tipping hazard. Can cause equipment damage, injury and 

death.
Exercise extreme care when handling cabinets to avoid equipment damage or injury to 

personnel. The Dual-Lite TRX MBC’s weight ranges from 198 to 700 lb. (89.8 to 317.5 kg).
Locate center of gravity symbols

 and determine unit weight before handling each 

cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from 

vertical at all times.

Содержание Dual-Lite TRX MBC

Страница 1: ...Dual Lite TRX MBC User Manual 10 30kVA 60Hz...

Страница 2: ......

Страница 3: ...orque Requirements 19 FIGURES Figure 1 Cabinet arrangement Dual Lite TRX UPS battery cabinets maintenance bypass cabinet 7 Figure 2 One line diagram single input three breaker Dual Lite TRX MBC 10 30k...

Страница 4: ...13 Table 6 Dual Lite TRX MBC specifications 16 Table 7 Dimensions for Dual Lite TRX UPS with Dual Lite TRX MBC 16 Table 8 Additional weight for Dual Lite TRX 10 30kVA UPS with internal batteries 17 T...

Страница 5: ...heck for voltage with both AC and DC voltmeters prior to making contact AVERTISSEMENT Le centre de gravit lev des appareils pr sente un risque de renversement lors des d placements pouvant entra ner d...

Страница 6: ...NT Risque d arc ou de d charge lectrique pouvant entra ner des dommages mat riels des blessures et m me la mort Les pr cautions de s curit habituelles suffisent lorsque le syst me est en mode de fonct...

Страница 7: ...diately Verify that the correct equipment is being installed The equipment supplied has an identification tag on the back of the main door reporting the type size and main calibration parameters of th...

Страница 8: ...capable of supporting its weight for instance check that doorways lifts ramps etc are adequate and that there are no impassable corners or changes in the level of corridors Ensure that the cabinet wei...

Страница 9: ...ent is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading 1 5 Cable Entry Cables can enter the Dual Lite TRX MBC from the bottom...

Страница 10: ...rounding conductor should be sized according to local or NEC codes cable lengths type of protection etc The grounding cable connecting the UPS to the main ground system must follow the most direct rou...

Страница 11: ...ps attached to the UPS The 600mm maintenance bypass cabinet ships separately from the UPS Dual Lite TRX UPS Dual Lite TRX UPS Dual Lite TRX UPS Maintenance Bypass Cabinet Matching Battery Cabinet Matc...

Страница 12: ...o follow adequate grounding procedures can result in electric shock hazard to personnel and the risk of fire should a ground fault occur AVERTISSEMENT Risque de d charge lectrique pouvant entra ner de...

Страница 13: ...e X9 J23 and J26 Tighten the connections to the proper torque see Table 14 8 Replace the panels Notes Refer to the Dual Lite TRX UPS installation manual SL 25648 for additional details about the Dual...

Страница 14: ...and bypass must share the same single source 3 A neutral is required from the system AC input source A full capacity neutral conductor is recommended Grounding conductors are recommended 4 Bypass and...

Страница 15: ...VA system Dual Lite TRX MBC Breaker Configuration Configured Breaker 3 BIB MBB MIB Table 3 Terminal block details 200mm Dual Lite TRX MBC three breakers 10 30kVA system Terminal Block Single Input Sys...

Страница 16: ...Top and bottom cable entry available through removable access plates Remove punch to suit conduit size and replace 5 Unit bottom is structurally adequate for forklift handling 6 Control wiring and pow...

Страница 17: ...0kVA system Terminal Block Single Input System TB2 Input TB3 Output NOTES 1 All dimensions are in inches mm 2 Control wiring and power wiring must be run in separate conduits 3 All wiring is to be in...

Страница 18: ...ng 703 704 706 8 Shown is typical for a four breaker configuration Also available a two breaker configuration MIB MBB and a three breaker configuration BIB MIB MBB MBB See Note 6 Customer Feed Output...

Страница 19: ...stallation Drawings 15 Dual LIte TRX MBC Figure 8 Solenoid key release unit 200mm Dual Lite TRX MBC K0 K1 K2 TB1 Fuseblock for SKRU Solenoid key release unit is mounted between the BIB and MBB breaker...

Страница 20: ...ree of Protection for UPS Enclosure IP 20 with and without front door open Standards and Conformities UL1778 5th Edition CSA 22 2 107 3 14 ISTA Procedure 1H WEEE Minimum Clearance Top in mm 24 610 Min...

Страница 21: ...ut Bypass and AC output Recommended cable sizes are suitable for operation at a maximum temperature of 104 F 40 C Table 10 Dual Lite TRX MBC input currents single input main Voltage 3 Ph 60 Hz MBC Rat...

Страница 22: ...kcmil 54179 60160 350kcmil 256 30695 112 400kcmil 256 30695 1403 500kcmil 256 30695 339 Table 13 Recommended lug sizes Compression Type M12 1 2 bolt Cable Size T B Copper Two Hole T B Aluminum Two Hol...

Страница 23: ...e these values unless the equipment is labeled otherwise Table 14 Busbar torque for power wiring Bolt Shaft Size Torque Lb in Nm 3 8 M10 192 22 1 2 M12 428 48 Table 15 Terminal block torque with compr...

Страница 24: ...DL 25652_REV0_02 16 Dual Lite TRX MBC User Manual 10 30kVA 60Hz...