Important Safety Instructions

Dual-LIte

®

 TRX

 MBC

2

Read this manual thoroughly before working with the Maintenance Bypass Cabinet. Retain this 

manual for use by installing personnel.

!

WARNING

Risk of arc flash and electric shock. Can cause equipment damage, injury and death.
Under typical operation and with all doors closed, only normal safety precautions are 

necessary. The area around the system should be kept free of puddles of water, excess 

moisture and debris.
Special safety precautions are required for procedures involving handling, installation and 

maintenance of the Maintenance Bypass Cabinet. Observe all safety precautions in this 

manual before handling or installing the Maintenance Bypass Cabinet. Observe all 

precautions in the Operation and Maintenance Manual, before as well as during performance 

of all maintenance procedures.
This equipment contains circuits that are energized with high voltage. Only test equipment 

designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always 

check with an AC and DC voltmeter to ensure safety before making contact or using tools. 

Even when the power is turned Off, dangerously high potential electric charges may exist.
All power and control wiring should be installed by a qualified electrician. All power and 

control wiring must comply with the NEC and applicable local codes.
ONLY properly trained and qualified personnel should perform maintenance on the Maintenance 

Bypass Cabinet. When performing maintenance with any part of the equipment under power, 

service personnel and test equipment should be standing on rubber mats. The service personnel 

should wear insulating shoes for isolation from direct contact with the floor ground.
One person should never work alone, even if all power is removed from the equipment. A 

second person should be standing by to assist and summon help in case of an accident.

!

AVERTISSEMENT

Risque d’arc ou de décharge électrique pouvant entraîner des dommages matériels, des 

blessures et même la mort.
Les précautions de sécurité habituelles suffisent lorsque le système est en mode de 

fonctionnement normal et que toutes les portes sont fermées. La zone entourant le système 

doit être exempte de flaques d’eau, d’humidité excessive et de débris.
Des précautions de sécurité spéciales sont requises pour les procédures associées à la 

manutention, à l’installation et à l’entretien de l’armoire de dérivation d’entretien. Observez 

toutes les précautions de sécurité décrites dans le présent manuel avant de manipuler ou 

d’installer l’armoire de dérivation d’entretien. Observez également toutes les précautions 

décrites dans le manuel d’utilisation et d’entretien, avant et pendant toutes les procédures 

d’entretien.
Cet équipement comporte des circuits à haute tension. Seuls des équipements d’essai conçus 

pour le dépannage doivent être utilisés. Cette mise en garde couvre notamment les 

oscilloscopes. Utilisez toujours un voltmètre c.a. et c.c. pour vérifier les tensions avant 

d’établir un contact ou d’utiliser des appareils. Des tensions dangereusement élevées peuvent 

demeurer dans le système même une fois l’alimentation coupée.
Tous les câbles d’alimentation et de contrôle doivent être installés par un électricien qualifié. 

Tous les câbles d’alimentation et de contrôle doivent être conformes au Code national de 

l’électricité des États-Unis (NEC) et ainsi qu’aux codes locaux en vigueur.
L’entretien de l’armoire de dérivation d’entretien ne doit être confié qu’à des professionnels 

qualifiés et dûment formés. Les responsables de l’entretien et l’équipement d’essai doivent 

reposer sur des tapis de caoutchouc lors de toute intervention sur une pièce d’équipement sous 

tension. Les responsables de l’entretien doivent porter des chaussures isolantes pour prévenir 

tout contact direct avec le plancher.
Une personne ne devrait jamais travailler seule, même si toute l’alimentation de l’équipement 

est coupée. Une deuxième personne devrait toujours être présente pour porter assistance ou 

chercher de l’aide en cas d’accident.

Содержание Dual-Lite TRX MBC

Страница 1: ...Dual Lite TRX MBC User Manual 10 30kVA 60Hz...

Страница 2: ......

Страница 3: ...orque Requirements 19 FIGURES Figure 1 Cabinet arrangement Dual Lite TRX UPS battery cabinets maintenance bypass cabinet 7 Figure 2 One line diagram single input three breaker Dual Lite TRX MBC 10 30k...

Страница 4: ...13 Table 6 Dual Lite TRX MBC specifications 16 Table 7 Dimensions for Dual Lite TRX UPS with Dual Lite TRX MBC 16 Table 8 Additional weight for Dual Lite TRX 10 30kVA UPS with internal batteries 17 T...

Страница 5: ...heck for voltage with both AC and DC voltmeters prior to making contact AVERTISSEMENT Le centre de gravit lev des appareils pr sente un risque de renversement lors des d placements pouvant entra ner d...

Страница 6: ...NT Risque d arc ou de d charge lectrique pouvant entra ner des dommages mat riels des blessures et m me la mort Les pr cautions de s curit habituelles suffisent lorsque le syst me est en mode de fonct...

Страница 7: ...diately Verify that the correct equipment is being installed The equipment supplied has an identification tag on the back of the main door reporting the type size and main calibration parameters of th...

Страница 8: ...capable of supporting its weight for instance check that doorways lifts ramps etc are adequate and that there are no impassable corners or changes in the level of corridors Ensure that the cabinet wei...

Страница 9: ...ent is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading 1 5 Cable Entry Cables can enter the Dual Lite TRX MBC from the bottom...

Страница 10: ...rounding conductor should be sized according to local or NEC codes cable lengths type of protection etc The grounding cable connecting the UPS to the main ground system must follow the most direct rou...

Страница 11: ...ps attached to the UPS The 600mm maintenance bypass cabinet ships separately from the UPS Dual Lite TRX UPS Dual Lite TRX UPS Dual Lite TRX UPS Maintenance Bypass Cabinet Matching Battery Cabinet Matc...

Страница 12: ...o follow adequate grounding procedures can result in electric shock hazard to personnel and the risk of fire should a ground fault occur AVERTISSEMENT Risque de d charge lectrique pouvant entra ner de...

Страница 13: ...e X9 J23 and J26 Tighten the connections to the proper torque see Table 14 8 Replace the panels Notes Refer to the Dual Lite TRX UPS installation manual SL 25648 for additional details about the Dual...

Страница 14: ...and bypass must share the same single source 3 A neutral is required from the system AC input source A full capacity neutral conductor is recommended Grounding conductors are recommended 4 Bypass and...

Страница 15: ...VA system Dual Lite TRX MBC Breaker Configuration Configured Breaker 3 BIB MBB MIB Table 3 Terminal block details 200mm Dual Lite TRX MBC three breakers 10 30kVA system Terminal Block Single Input Sys...

Страница 16: ...Top and bottom cable entry available through removable access plates Remove punch to suit conduit size and replace 5 Unit bottom is structurally adequate for forklift handling 6 Control wiring and pow...

Страница 17: ...0kVA system Terminal Block Single Input System TB2 Input TB3 Output NOTES 1 All dimensions are in inches mm 2 Control wiring and power wiring must be run in separate conduits 3 All wiring is to be in...

Страница 18: ...ng 703 704 706 8 Shown is typical for a four breaker configuration Also available a two breaker configuration MIB MBB and a three breaker configuration BIB MIB MBB MBB See Note 6 Customer Feed Output...

Страница 19: ...stallation Drawings 15 Dual LIte TRX MBC Figure 8 Solenoid key release unit 200mm Dual Lite TRX MBC K0 K1 K2 TB1 Fuseblock for SKRU Solenoid key release unit is mounted between the BIB and MBB breaker...

Страница 20: ...ree of Protection for UPS Enclosure IP 20 with and without front door open Standards and Conformities UL1778 5th Edition CSA 22 2 107 3 14 ISTA Procedure 1H WEEE Minimum Clearance Top in mm 24 610 Min...

Страница 21: ...ut Bypass and AC output Recommended cable sizes are suitable for operation at a maximum temperature of 104 F 40 C Table 10 Dual Lite TRX MBC input currents single input main Voltage 3 Ph 60 Hz MBC Rat...

Страница 22: ...kcmil 54179 60160 350kcmil 256 30695 112 400kcmil 256 30695 1403 500kcmil 256 30695 339 Table 13 Recommended lug sizes Compression Type M12 1 2 bolt Cable Size T B Copper Two Hole T B Aluminum Two Hol...

Страница 23: ...e these values unless the equipment is labeled otherwise Table 14 Busbar torque for power wiring Bolt Shaft Size Torque Lb in Nm 3 8 M10 192 22 1 2 M12 428 48 Table 15 Terminal block torque with compr...

Страница 24: ...DL 25652_REV0_02 16 Dual Lite TRX MBC User Manual 10 30kVA 60Hz...