background image

HZ-9003C

Multifunctional Partial Discharge

Tester

Huazheng Electric Manufacturing(Baoding) Co,.Ltd

Содержание HZ-9003C

Страница 1: ...HZ 9003C Multifunctional Partial Discharge Tester Huazheng Electric Manufacturing Baoding Co Ltd...

Страница 2: ...manual and operate and maintain the instrument according to the manual to prolong its service life Just a light press the test will be completed automatically is the operating characteristics of this...

Страница 3: ...Contents I Adoption standard 1 II Operation Notice 1 III Overview 1 IV Measurement Procedures 9 VI Maintenance 24 VII Packing List 25...

Страница 4: ...ameter settings to ensure the measurement accuracy 3 If needs to replace sensors during the testing should turn off the output voltage 4 During the testing should handle the device with care to avoid...

Страница 5: ...e workers to make evaluation timely for the switchgear cabinet operation status and thus greatly improve the equipment operation reliability safety and effectiveness HZ 9003C Multifunctional Partial D...

Страница 6: ...Trig menu 12 LEVEL Adjust trigger level 13 TIME DIV Time base 14 POSITION Adjust level trigger position 15 HORI Level menu 16 VERTICAL Adjust vertical position 17 VOLTS Voltage shift 18 Power Switch...

Страница 7: ...ton to power on wait for 30 seconds the tester will be started the start button will be in yellow light 2 Off Press and hold down the start button to stop the main tester The tester is off when the ma...

Страница 8: ...locked turn brighter means USB is connected if grey means no USB Turn bright When connected with PC by USB otherwise it is grey 1 5 Menu Press Menu button menu bar is shown at the bottom of the displ...

Страница 9: ...ultrasonic wave signal UHF Output UHF signal CT Output to ground current signal Close If only one channel is required for detection then the other channel can be closed If channel1 channel2 is closed...

Страница 10: ...channel discharge amount mv dB dbmW dBuV dBmV Press Unit F2 key to change the current channel discharge Unit This option is circular selection the unit selection can be determined by the discharge det...

Страница 11: ...trigger mode F4 Key to make change of the current channel trigger mode Trigger Mode Select trigger mode Trigger mode can be automatic normal and single trigger At default condition the Multifunctional...

Страница 12: ...easurement Procedures When use the Multifunctional Partial Discharge Tester and with one sensor for testing select Channel 1 to conduct detect When use two sensor for detection then use Channel2 Be no...

Страница 13: ...ess F2 key to setup output voltage and unit When use composite TEV sensors for detection the output voltage must be required 3 Start Measurement Press AUTORANGE button the tester is starting to measur...

Страница 14: ...dio signal even near highway traffic These sources can produce instantaneous earth voltage signals to the metals such as substation doors or fences without touching or connecting Therefore the backgro...

Страница 15: ...r middle and high voltage switches shall be recorded down If these switches are in disconnected position then the components would not be electrified there will be no measurement readings of them Reco...

Страница 16: ...cy current transformer BNC end High frequency current transformer connection 2 Tester settings Open the tester press and select the current channel to CH1 Press MENU key then press F1 key to select di...

Страница 17: ...s too large the value at the screen will then turn red at this moment the sensor is in saturation state Sensor Saturated 4 Save To save the current discharged signal You need to prepare a USB disk to...

Страница 18: ...to close the menu bar if the menu bar is popping up AUTORANGE Close 4 3 Ultrasonic Measurement Mainly support the measurement of transformer inside partial discharge 1 Ultrasonic sensor connection Use...

Страница 19: ...hen press F1 key to select discharge test as HFCT press F2 Key to set output voltage and unit When use ultrasonic sensor to conduct measurement it would require output voltage 3 Start measurement Pres...

Страница 20: ...the tester and select USS ultrasonic mode plug the headset and adjust volume The readings will be displayed at the screen Take measurement of the background noise At any case should follow the safe d...

Страница 21: ...Discharge 1 Ultra high frequency sensor connection Use BNC SMA cable to connect to the tester CH1 channel BNC port the other SMA end to the ultrahigh frequency cable OUT 12V Port Ultra high frequency...

Страница 22: ...will be then at automatic trigger state the Channel 1 screen will display the current ultra high frequency sensor testing discharge signals Non discharge Signals with discharge signals When the disch...

Страница 23: ...sing the automatic trigger Press Menu off to close the menu bar if the menu bar is popping up AUTORANGE Close 4 5 Two Channels testing If use two channels for testing you should connect two sensors Op...

Страница 24: ...Press F2 key to set output voltage and unit Use the composite TEV sensor for testing shall set the output voltage Press CH2 to select current channel at Channel2 then press Menu key and F1 key to set...

Страница 25: ...5 2 5 Save To save the current discharged signal You need to prepare a USB disk to store the graphics Save Graphics Press SAVE RECALL open the save recall menu bar press graphic F5 key to save the dis...

Страница 26: ...value SPL Sensor central fequency 20 50kHz Sensor diameter no more than 50mm Heterodyne frequency 38 4kHz 4 Non contact ultrasonic energy collector Effective acceptance distance 30m Sensor center freq...

Страница 27: ...en store or place the main tester don t expose the LCD display to the direct sunlight for long time Note To avoid damage the main tester don t place the tester in fog liquid or solvent environment 6 2...

Страница 28: ...scharge Tester host 1 2 U disk 1 3 TEV sensor 1 4 Ultrasonic sensor GIS 1 5 Ultrasonic sensor transformer 1 6 Ultrasonic concentrator 1 7 High frequency current transformer 1 8 Ultrahigh frequency sen...

Отзывы: