UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
186
Figure 5-54
Parameters associated with intelligent power on the WebUI 6
lists the parameters associated with intelligent power.
Table 5-3
Parameters associated with intelligent power
Parameter
Value
Remarks
Working mode
ECO
N/A
D.G. mode
Enable
You cannot change the value.
Intra-rack power module start
delay (s)
5
N/A
Input adaptability
Strong
N/A
Output freq. track rate (Hz/s)
0.6
N/A
D.G. connection [GEN]
Enable
N/A
MUS05A DO_4
D.G. control
N/A
ATS
Connected
N/A
D.G. startup batt. volt. (V/cell)
1.80
N/A
D.G. power limiting (kVA)
N/A
Indicates the actual D.G. power.
Set it as required.
D.G. charger power ratio (%)
N/A
Indicates the percentage of the
battery power provided by the
charger. Set it as required.
In battery mode (not battery test state), when the battery voltage reaches
D.G. startup batt. volt.
or
Low battery voltage
, the UPS triggers D.G. startup signals.
In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the UPS triggers D.G. shutdown signals.