UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
178
Figure 5-39
Hibernation parameters on the WebUI
Step 3
On the WebUI, set
Paral. sys. hibernate
to
Enable
, and click
Submit
. A security waning is
displayed, and click
OK
.
Step 4
Set the
Module cycle hiber. period (days)
parameter to an integer ranging from
0
to
100
.
The default value is
30
.
Click
Submit
after you set the parameter on the WebUI.
----End
5.3 Setting Intelligent Power Mode
Before you connect the D.G. to a UPS system, check that the system is a single UPS system
and that the system is working in non-inverter mode and has connected to batteries.
When the UPS is working, the D.G. starts if a mains outage occurs and the battery voltage
reaches the specified threshold. You can set intelligent power mode on the LCD or WebUI.
5.3.1 LCD
Procedure
Step 1
On the main screen, tap
System Info.
and
. The
Settings
screen is displayed.
If you have not logged in, enter a user name and password, and tap
on the login screen
displayed.
Step 2
On the
Settings
screen, tap
Intelli. Power
.