UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
179
Figure 5-40
Intelli. Power screen
Step 3
Set
Intelligent power
to
Enabled
. In the warning dialog box, tap
Yes
.
Figure 5-41
Intelligent power parameters on the LCD
Intelligent Power
The value can be
Enabled
or
Disabled
. The intelligent power supply function can be
used only when
Intelligent power
is set to
Enable
. The default value is
Disabled
.
ATS
The value can be
Connected
or
Not connected
. When the value is
Connected
, the UPS
works in the ATS scenario; when the value is
Not connected
, the UPS works in the reuse
scenario. The default value is
Connected
. This parameter is available only after you set
Intelligent Power
to
Enabled
.
D.G. startup batt. volt. (V/cell)
The value ranges from
1.80
to
2.00
. The default value is
1.80
. This parameter is available
only after you set
Intelligent Power
to
Enabled
.
When the D.G. is connected, ensure that the preceding three parameters have been set so that the UPS
can run properly.