4 Control Panel
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
48
Name
LCD
Function
Replace Batteries
Clears all the battery
data after you replace
batteries.
Restore Default
Settings
Restores default
settings after you shut
down the inverter.
4.6.2 Setting Menu
The configured number of batteries must match the actual number. When the actual number
changes, change the configured number. If the configured number is less than the actual
number, the battery lifespan is shortened. If the configured number is greater than the actual
number, battery leakage may cause a fire.
On the default screen, press
and then
▲
to enter the setting menu, as shown in
. On the parameter setting screen, press
and then
▲
to select a parameter and
press
.