UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
5 Operations
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
63
Step 10
After checking that the system is running properly, turn on the load switch to start the load.
To prevent triggering overload protection, start the loads with higher power and then loads with lower
power.
----End
Starting the UPS in Battery Mode
Step 1
Close the external battery circuit breakers (if any), or connect battery cables.
Step 2
Press
on each control panel.
Step 3
After the LCD screen lights up for 1s, the initialization screen is displayed. After the progress
bar is complete, the default screen is displayed, as shown in
Figure 5-9
Power-on and default screen
Step 4
Set the voltage level based on the actual output voltage. The voltage level can be set to 220 V
(default), 230 V, or 240 V.
Figure 5-10
Setting the voltage level
Step 5
Set the system output frequency level based on the rated frequency. The values include 50 Hz
(default), 60 Hz, and Automatic.