UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
4 Control Panel
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
56
Name
Screen
Function
Value
Range
Preset
Value
Remarks
Frequency
range
ECO frequency
range. In ECO
mode, when the
difference between
the bypass
frequency and the
rated frequency is
greater than this
range, the system
determines that the
ECO frequency is
abnormal and
transfers to normal
mode.
The frequency
range must be less
than the bypass
frequency range.
±0.5 Hz, ±1
Hz, ±2 Hz,
and ±3 Hz
2 Hz
The value is
configurable
only after the
inverter shuts
down.
DSP
version
number
DSP version
number, which can
be viewed and
cannot be set
N/A
N/A
The version
number only
can be viewed
and cannot be
set.
CPLD
version
number
CPLD version
number, which can
be viewed and
cannot be set
N/A
N/A
The version
number only
can be viewed
and cannot be
set.
4.6.3 Active Alarm Display Menu
On the default screen, press
and then
▲
to enter the active alarm display menu, as