A Technical Specifications
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
85
Item
Specifications
Battery compartment: IP55
Installation mode
Can be installed on a floor, rooftop, and wall, but cannot be stacked
or installed along a pole.
Maintenance mode
Operated and maintained from the front
Cable routing
Routed in and out from the bottom
A.5 HXC150S Heat Exchanger Specifications
Table A-5
HXC150S heat exchanger specifications
Item
Specifications
Maximum power consumption
136 W
Typical power consumption
100 W
Heat exchanging capacity
140 W/K
Input voltage
-48 V DC
Operating temperature
-40°C to +45°C
Storage temperature
-40°C to +70°C
Alarm reporting
Generates alarms over the dry contact. If no alarm is
generated, the dry contact is closed. If an alarm is
generated, the dry contact is open.
Altitude
< 4000 m
Relative humidity
5% RH to 100% RH
Noise
< 65 dB(A)
A.6 TEC04C Specifications
Table A-6
TEC04C specifications
Item
Specifications
Rated voltage
-48 V DC
Rated cooling capacity (L32/L32)
200 W
Heating capacity
> 300 W
Rated Cooling Power Consumption
300 W
Operating environment
-40°C to +40°C