TP48200A-HT19C3 and TP48200A-HT19C4 Telecom
Power
User Manual
2 Overview
Issue 03 (2019-11-15)
Copyright © Huawei Technologies Co., Ltd.
18
Item
TP48200A-HT19C3
TP48200A-HT19C4
(Optional) AC output circuit
breaker
One 2-pole 10 A circuit breaker and one 3-pole maintenance socket
protected by an 10 A electric residual current device (RCD).
DC output
Battery low voltage disconnection (BLVD): two 1-pole 10 A circuit
breakers and four 1-pole 16 A circuit breakers
Load low voltage disconnection (LLVD): one 1-pole 100 A circuit
breaker, one 1-pole 63 A circuit breaker, and four 1-pole 32 A circuit
breakers
Battery route: two 1-pole 125 A circuit breakers
Rectifier
A maximum of four R4850G2s or R4830G2s can be configured.
SMU
One SMU02B
UIM
One UIM02C
Sensor
Mandatory: one battery temperature sensor, one ambient temperature
sensor in the equipment compartment, and one door status sensor
Optional: one smoke sensor, one ambient temperature and humidity
sensor, and one water sensor.
(Optional) Intelligent electric meter One intelligent electric meter and one current transformer
(Optional) Bluetooth door lock
One electric door lock and one Bluetooth controller
Battery
The battery compartment with two layers supports a maximum of two 12
V, 150 Ah battery strings.
Maximum output power
12 kW
Class C environments refer to sea environments or outdoor land environments (with simple shielding
measures) near pollution sources. If a site is near a pollution source, it is at most 3.7 km away from salt
water, such as the sea and salt lakes, 3 km away from heavy pollution sources, such as smelteries, coal
mines, and thermal power plants, 2 km away from medium pollution sources, such as chemical, rubber,
and galvanization industries, and 1 km away from light pollution sources, such as packing houses,
tanneries, and boiler rooms.