Installing the Air Duct
Step 1 Wear an ESD wrist strap. For details, see
.
Step 2 Power off the server. For details, see
.
Step 3 Remove the power cables. For details, see
Step 4 Remove the server. For details, see
5.4.4 Removing the Server and Guide Rails
.
Step 5 Remove the chassis cover. For details, see
Step 6 (Optional) If a full-height full-length riser module is installed in I/O module 1 or
2, remove it. For details, see
.
Step 7 Take a spare air duct out of its ESD bag.
Step 8 Align the positioning pins on the air duct with the fixing holes on the chassis
according to the instructions on the air duct. Vertically place the air duct
downwards. See
Figure 5-37 Installing the air duct
Step 9 If a supercapacitor is required, connect the cable between the supercapacitor and
RAID controller card. See
TaiShan 200 Server
Maintenance and Service Guide (Model 2280)