No.
Parameter
Description
Remarks
14
VRT exit
hysteresis
threshold
Specifies the LVRT/HVRT recovery threshold.
● This parameter is
displayed when
LVRT or HVRT is
set to Enable.
● LVRT recovery
threshold =
Threshold for
triggering LVRT +
VRT exit hysteresis
threshold
● HVRT recovery
threshold =
Threshold for
triggering HVRT +
VRT exit hysteresis
threshold
15
Grid voltage
jump
triggering
threshold (%)
Specifies the LVRT or HVRT threshold for
triggering a transient voltage jump of a power
grid. A transient voltage jump indicates that the
inverter cannot immediately disconnect from
the power grid when the power grid is
abnormal due to transient changes.
-
16
Zero current
due to power
grid fault
Certain countries and regions have
requirements on the output current during
high/low voltage ride-through. In this case, set
this parameter to Enable. After this parameter
is set to Enable, the output current is less than
10% of the rated current during high/low
voltage ride-through.
This parameter is
displayed when LVRT
or HVRT is set to
Enable.
17
Active
islanding
protection
Specifies whether to enable the active islanding
protection function.
-
18
Automatic
OFF due to
communicati
on
interrupted
The standards of certain countries and regions
require that the inverter must shut down after
the communication is interrupted for a certain
time.
-
19
Automatic
ON due to
communicati
on resumed
If this parameter is set to Enable, the inverter
automatically starts after communication
recovers. If this parameter is set to Disable, the
inverter needs to be started manually after
communication recovers.
-