5.5 (Optional) Installing the Power Cable of the
Tracking System
Precautions
NO TICE
● A switch-disconnector-fuse or fuse-switch-disconnector with a voltage of no
less than 800 V, current of 16 A, and protection type of gM needs to be
installed between the inverter and the tracker controller for protection.
● The cable between the wiring terminal on the power cable and the switch-
disconnector-fuse or fuse-switch-disconnector should be less than or equal to
2.5 m.
● Connect the power cable of the tracking system before the AC output power
cable. Otherwise, reworking will be caused.
Cable Specifications
Recommended: dual-layer three-core outdoor copper cable with a conductor
cross-sectional area of 10 mm2 and a cable outer diameter of 15–18 mm.
Procedure
Step 1 Connect the power cable of the tracking system to the terminal block.
Figure 5-4 Cable connection
----End
SUN2000-(196KTL-H0, 200KTL-H2, 215KTL-H0)
User Manual
5 Electrical Connections
Issue 02 (2020-10-30)