Figure 7-10 Power grid parameters (special user)
----End
Parameters
No.
Parameter
Description
1
Grid Code
Set this parameter based on the grid code of the country
or region where the inverter is used and the inverter
application scenario.
2
Isolation settings
Set the working mode of the inverter based on the
grounding status at DC side and the connection to the
power grid.
3
Output mode
Specifies whether the inverter output has a neutral wire
based on the application scenario.
4
Automatically start upon
grid recovery
Specifies whether to allow the inverter to automatically
start after the power grid recovers.
5
Grid connected recovery
time from grid faults (s)
Specifies the time after which the inverter begins
restarting after the power grid recovers.
6
Grid reconnection voltage
upper limit (V)
The standards of certain countries and regions require
that after the inverter shuts down for protection due to a
fault, if the power grid voltage is higher than Grid
reconnection voltage upper limit, the inverter is not
allowed to reconnect to the grid.
7
Grid reconnection voltage
lower limit (V)
The standards of certain countries and regions require
that after the inverter shuts down for protection due to a
fault, if the power grid voltage is lower than Grid
reconnection voltage lower limit, the inverter is not
allowed to reconnect to the grid.
SUN2000-(196KTL-H0, 200KTL-H2, 215KTL-H0)
User Manual
7 Man-Machine Interactions
Issue 02 (2020-10-30)
Copyright © Huawei Technologies Co., Ltd.
61