RMS-SNMP01B SNMP Card
User Manual
9 Protecting the Server by Using the RCCMD Software
Issue 10 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
51
Whether the RCCMD SSL encrypted transmission is enabled on the WebUI of UPS2000
SNMP card and RCCMD client is irrelevant to the heartbeat detection function. Only when
the SSL encryption is enabled on the RCCMD client, the logs recorded by the RCCMD client
are marked with "(SSL...)".
On the RCCMD client, the IP address of the SNMP card that detects heartbeat needs to be
added. Then the UPS alive check function is supported and the RCCMD can check whether
the UPS and RCCMD communicate properly. The RCCMD client can also receive messages
sent by the SNMP card.
Procedure
Step 1
On the RCCMD client, add the IP address of the SNMP card that detects heartbeat, as shown
in
Step 2
The UPS2000 SNMP card supports both ways of detecting heartbeats. If the job configured
for the SNMP card event is set to
RCCMD TRAP
, the RCCMD client needs to be set to
by
the use of CS121/UPSMAN Traps
. If
by polling CS121/UPSMAN every x seconds…
is
selected as the method of detecting heartbeats, set the detection method. The default interval
is 1800s and detection is performed 100 times, as shown in
Figure 9-2
Heartbeat detecting mode on the RCCMD client
You can also manually detect heartbeat by clicking
Run alive check now...
, as shown in