9 Protecting the Server by Using the RCCMD Software
Issue 10 (2020-03-20)
Copyright © Huawei Technologies Co., Ltd.
50
Figure 9-1
Setting the SNMP card IP address on the RCCMD client and SSL encrypted
transmission mode
Step 2
On the SNMP card WebUI, choose
Config
>
RCCMD
, and set
RCCMD shutdown
to
Enabled
. For details, see
Step 3
On the SNMP card WebUI, the SSL encryption is
Enabled
by default and does not need to be
set. If the RCCMD client is set to the unencrypted mode, you need to set the SSL encryption
to
Disabled
on the SNMP card WebUI.
Step 4
Configure events. If you set the job type to
RCCMD Message
under
Inverter on
, specify the
IP address and port of the RCCMD client. The port is 6003 by default. If you need to modify
the port, modify the port on the RCCMD client at the same time to keep them the same. Enter
the message to be sent and set the message sending mechanism. For example, set it to
Immediately, once
.
Step 5
On the
Monitoring
>
Control
page, start the UPS, and the inverter mode will be triggered.
Send the message indicating that the inverter is on.
Step 6
On the RCCMD client, you can check the log in the upper left corner of the RCCMD client
page.
----End
9.3 UPS Alive Check Function