PDU8000-(0125, 0250, 0400, 0630, 0800)
DCV8-BXA001 Battery Circuit Breaker Box
User Manual
3 Installation
Issue 03 (2019-05-20)
Copyright © Huawei Technologies Co., Ltd.
14
3.2.3 Cables
Prepare battery cables before installation as required. You can prepare cables based on the
recommended specifications in this section after the following requirements are met:
Cables are routed on the wall or on the floor, the ambient temperature is 30°C, the DC
voltage drop is less than 1%, and the length of DC cables does not exceed 40 m.
When the installation environment (such as routing mode and ambient temperature)
changes, prepare cables according to IEC60364-5-52 or local standards.
Use double-insulated polyethylene copper cables. The current-carrying capacity is
calculated based on polyethylene copper cables.
If cables are provided by customers, the cables must be double-insulated and meet 1000
V DC voltage withstanding and current-carrying capacity requirements.
PDU8000-0125DCV8-BXA001 Cables
Table 3-1
Specifications for PDU8000-0125DCV8-BXA001 cables and terminals
Terminal Number of
Terminals and
Hole Diameter
Recommended
Cable
Specifications
Recommended
Wiring
Terminal
Bolt
Specifications
Recommended
Cable Color
UPS +
1 x M8
(through-hole)
1 x 35 mm
2
35-M8
M8 x 25
Red
UPS N
1 x M8
(through-hole)
1 x 35 mm
2
35-M8
M8 x 25
Blue
UPS–
1 x M8
(through-hole)
1 x 35 mm
2
35-M8
M8 x 25
Black
BAT+
1 x M8
(through-hole)
1 x 35 mm
2
35-M8
M8 x 25
Red
BAT N
1 x M8
(through-hole)
1 x 35 mm
2
35-M8
M8 x 25
Blue
BAT–
1 x M8
(through-hole)
1 x 35 mm
2
35-M8
M8 x 25
Black
PE
1 x M6 (rivet
nut)
1 x 16 mm
2
16-M6
M6 x 16
Green-and-yellow
PDU8000-0250DCV8-BXA001 Cables
Table 3-2
Specifications for PDU8000-0250DCV8-BXA001 cables and terminals
Terminal
Number of
Terminals
and Hole
Diameter
Recommended
Cable
Specifications
Recommended
Wiring
Terminal
Bolt
Specifications
Recommended
Cable Color