PDU8000-(0125, 0250, 0400, 0630, 0800)
DCV8-BXA001 Battery Circuit Breaker Box
User Manual
3 Installation
Issue 03 (2019-05-20)
Copyright © Huawei Technologies Co., Ltd.
30
No.
Description
8
GND
Table 3-9
Mapping relationship of ports
MUE05A BCB
BIB J1
Description
OL
5 OL
BCB box connected
STA
6 STA
BCB box circuit breaker state
DRV
7 DRV
BCB box trip control
0V
8 GND
signal grounding
Step 2
After connecting the signal cable, set toggle switch 1 to ON and toggle switch 2 to OFF for
the DIP switch on the control board.
Figure 3-15
DIP switch (old BIB board)
(1) Control signal port J1
(2) DIP switch S1