ME60
Hardware Description
1 Hardware Description
Issue 01 (2018-05-07)
117
Input upstream requirements
Protection components must be provided for PDFs to ensure that the rated AC/HVDC
current of each channel is not less than 14A.
Note the derating requirements of protection components when using protection components
such as fuses and circuit breakers.
The input circuit breakers of a PDF must match the output circuit breakers.
In HVDC application scenarios, ensure that the protection components meet HVDC certification and the
fuses and circuit breakers meet positive and negative pole protection.
If the front-end PDF does not provide enough power inputs, configure a PDB that meets
the following requirements:
−
The current of each channel output by the HVDC PDB is not less than 14A.
−
Double-channel backup is used.
−
The input current is not less than the sum of current of its connected output lines.
1.8.5.8 Switch
The switch controls the power output of PMs. The two switches back up each other. When
one or two switches are in the ON state, the power output of PMs is enabled.
Appearance
Figure 1-63 shows the appearance of the switch.
Figure 1-63
Switch
Panel
Table 1-77
Switch Description
Switch Name
Description
Содержание ME60 Series
Страница 1: ...ME60 V800R009C10SPC200 Hardware Description Issue 01 Date 2018 05 07 ...
Страница 47: ...ME60 Hardware Description 1 Hardware Description Issue 01 2018 05 07 38 Appearance Figure 1 11 Appearance ...
Страница 52: ...ME60 Hardware Description 1 Hardware Description Issue 01 2018 05 07 43 Appearance Figure 1 15 Appearance ...
Страница 58: ...ME60 Hardware Description 1 Hardware Description Issue 01 2018 05 07 49 Appearance Figure 1 19 Appearance ...
Страница 64: ...ME60 Hardware Description 1 Hardware Description Issue 01 2018 05 07 55 Appearance Figure 1 22 Appearance ...
Страница 155: ...ME60 Hardware Description 1 Hardware Description Issue 01 2018 05 07 146 Figure 1 86 Board ...