Installing an Internal Ground
Cable
3.1
Installing Internal DC
Terminals
3.2
Connect the ground
points of modules in
sequence, and secure
the ground cable using
a ground screw.
•
Connect cables in accordance with local installation laws and regulations.
•
Before connecting cables, ensure that the DC switch on the battery and all the switches
connected to the battery are set to OFF. Otherwise, the high voltage of the battery may result
in electric shocks.
3
Internal Electrical Connections of the Battery
•
Internal electrical cables are delivered with the battery, see the
Packing List in the packing case.
•
The Amphenol terminal is used as the DC terminal between the power control module and the
battery expansion modules.