FusionModule1000A40 ICT Solution
Maintenance Guide
4 Parts Replacement
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
83
Cut a pipe inside the air conditioner about 20 mm away from a turning point in the vertical
direction.
Cut a pipe outside the air conditioner about 40 mm away from the air conditioner base on
the vertical direction.
Figure 4-28
Cutting air conditioner pipes
(1) Cutting points on air conditioner pipes
Step 13
Move the air conditioner.
Steel plates and pipes must be placed a certain distance away from the pre-fab. module side
wall to prevent scratching the side wall.
1.
Take the fittings for moving the air conditioner from the pre-fab. module fitting bag.
Fittings for moving an air conditioner include a 3 mm thick steel plate, two 1.5 m long DN32 steel pipes,
and three 0.5 m long DN32 steel pipes.
2.
Place the 3 mm thick steel plate on the raised floor in the cold aisle.
3.
Place one 1.5 m long DN32 steel pipe above the 3 mm thick steel plate about 100 mm
away from the base of air conditioner D1.