FusionModule1000A40 ICT Solution
Maintenance Guide
4 Parts Replacement
Issue 01 (2019-03-05)
Copyright © Huawei Technologies Co., Ltd.
70
Preparations
Tools: flat-head screwdriver, Phillips screwdriver, adjustable wrench, socket wrench,
protective gloves, ESD floor suction plate, step ladder
Materials: spare air cooled in-row precision air conditioner
Documents:
NetCol5000-A 21 kW Air Cooled In-row Precision Air Conditioner Quick Guide
(208 V)
,
NetCol5000-A 25 kW Air Cooled In-row Precision Air Conditioner Quick Guide (300
mm Width)
, indoor/outdoor unit and T/H sensor wiring diagram, power supply and
distribution system diagram, cooling device initial configuration table
Skill requirement: cooling engineer
For the table, see the initial configuration parameter manual for the solution in use.
Procedure
Step 1
Locate the cold aisle containment where maintenance is to be performed based on the position
of the faulty air conditioner.
Step 2
Remove the suspended ceilings in the cold and hot aisles adjacent to the air conditioner.
Assign two persons to remove a suspended ceiling together. One person holds up the
suspended ceiling, while the other person removes the fasteners.
Figure 4-13
Removing a suspended ceiling
1.
Remove the sealing ring in the suspended ceiling above the front of the air conditioner.
2.
Remove the bolts securing the suspended ceiling using a Phillips screwdriver.