FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
4 Routine Maintenance
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
53
4.5.6 Other Systems
Table 4-20
Semi-annual maintenance checklist for other systems
Item
Method
Expected
Result
Troubleshooting
Lights
Check whether the
lights can be
switched on
normally.
Lights work
normally.
1.
If a light cannot be switched on,
check whether the light is
securely installed and in good
contact with the light base.
2.
If a light is securely installed and
in good contact with the light
base but fails to turn on, replace
the light.
Ventilation
vent air
filter
Check whether the
filter is blocked.
The air filter is
not blocked.
If an air filter is slightly blocked,
clean the air filter and reinstall it. If
more than 50% of the meshes are
blocked, perform replacement by
following instructions in
Replacing a Ventilation Vent Air
Filter
Cable trays
inside
containers
Check whether the
cable trays are
securely connected
without damage or
misshapen.
Cable trays are
properly
installed, and
fasteners are
secure.
Secure cable trays that have become
loose.
Cable trays,
screws, and
nuts are free
from rust or
corrosion.
Repaint corroded cable trays, or
replace damaged and seriously
corroded parts. For details, see the
installation guide for the
corresponding solution.
Cables
Check cable
connections.
Cables are
securely
connected
without bare
terminals.
Secure terminal connections, and
replace terminals that do not meet
requirements. For details, see the
installation guide for the
corresponding solution.
Check whether
cables are intact.
Cable
jackets are
free from
damage or
cracks.
No cable
overheats
due to
overload
and the
loads are
within the
rated
capacity of
Replace parts that do not meet
requirements.