Optical fibers of an optical cable
Cable
manager
Splice and coil optical fibers inside the splicing tray
Service
device
You are advised to bind and coil the redundant optical
fibers on the baffle plate of the equipment compartment.
All fibers must be routed over the
cablemanager so that the cabinet door will
not be hindered by protruding fibers when
being closed.
Connect the other end to
the device
Bend radius of an optical fiber is
greater than or equal to 40mm.
baffle plate
Binding strap of the
equipment compartment
54
6 Routing Cables