ETP48400-C9A2 Embedded Power
User Manual
7 Maintenance
Issue 05 (2020-04-07)
Copyright © Huawei Technologies Co., Ltd.
73
Figure 7-7
Replacing an AC SPD module
Step 4
Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist strap and ESD
gloves.
----End
Follow-up Procedure
Check that the alarm for the AC SPD is cleared.
7.4.5 Replacing a Circuit Breaker
Prerequisites
Before replacing an AC circuit breaker, switch off the upstream input circuit breaker.
The cabinet door key, insulation tape, and required tools are available.
The new circuit breaker is intact and has the same specifications as the circuit breaker to
be replaced.
Procedure
Step 1
Unscrew and remove the cover of the circuit breaker.
Step 2
Switch off the circuit breaker.
Step 3
Record the positions where the cables and signal cable terminals connect to the circuit
breaker.
Step 4
Loosen the screw that secures the upper port of the circuit breaker using a Phillips screwdriver,
and remove the power cable and signal cable terminals. Wrap the cable and terminals using
insulation tape.