2-56
l
Providing 10 switch value inputs (optical/electrical isolation).
l
Providing 6 relays (max. 5A/220V ) to drive external actuators.
l
Providing 2 PWM outputs (8bit resolution, basic clock no greater than 500kHz).
l
Driving of 7 independent collector open-circuit gates (absorption current
300mA).
l
Communication with BCKM through RS485 interface.
2.6.1 Alarm Box Input
l
Monitoring temperature: frequency type hygrothermograph.
l
Monitoring humidity: frequency type hygrothermograph.
l
Monitoring smoke: ionic smoke sensor or optical/electrical smoke sensor.
l
Monitoring naked flame (optional): flame detector or hyper-thermo detector.
l
Burglar proof monitoring: infrared monitor, optical/electrical monitor, door
magnetic monitor.
l
Other sensor inputs: Maximally 10 sensor inputs of the same type (except the
temperature and humidity sensors) can be supported.
2.6.2 Alarm Indicator
The 10 red indicator on the alarm box panel correspond to the following alarm
values:
l
Fire alarm: alarm generated due to over heat or by smoke detector.
l
Smoke alarm: overtime alarm generated by the smoke sensor.
l
Temperature upper limit: alarm generated when the ambient temperature
exceeds the upper limit.
l
Temperature lower limit: alarm generated when the ambient temperature
exceeds the lower limit.
l
Humidity alarm: alarm generated when the relative humidity is not in the
specified range.
l
Soaking: alarm generated when the soaking detector is triggered.
l
Air-conditioner status: alarm generated when a fault occurs to the
air-conditioner.
l
Optical/electrical: burglar alarm generated when the optical/electrical switch is
triggered.
l
Infrared: burglar alarm generated when the infrared sensor is triggered.
l
Door magnetic: generated burglar alarm generated when the door magnetic
switch is triggered.
When there are more than one input signals from the same type of sensors, they will
be regarded an alarm event. Maximally 10 sensors of the same type (except the