User Manual
Airbridge cBTS3612 CDMA Base Station
System Description
2 Hardware Architecture
2-51
2.5.2 General Structure
The -48V power is filtered by the EMI filter on top of the cabinet, and then goes
down along the wiring trough, and finally connected to the input bus bar of the
power subrack backplane. The power supply subsystem uses five +27V/65A DC/DC
power supply units (PSU) in full configuration. These five PSUs operation in 4+1
redundancy to ensure an output of at least 7200W. The size of PSU is L
%
W
%
H =
400mm
%
121.9mm
%
177.8mm.
The overall structure of the power supply system is shown in Figure 2-26.
Wiring terminals
-48VIN
GND
DC/DC
DC/DC
DC/DC
Power supply subrack
Switch box
-48V power supply indication
From cabinet-top LGND
DU
…
TRX0
PGND
RLDU1
TRX11
16 service units
RLDU0
RLDU2
Indicator PCB
DC/DC
DC/DC
...
...
Figure 2-26
Structure of power supply system
2.5.3 Technical Indices
I. DC input lightning protection
DC input lightning protection part is an external cabinet -top lightning arrester. It
mainly features:
l
Temperature-controlled fusing technology and built-in over-current protection
circuit to prevent fire.
l
Multiple autonomous current equalization technology used to withstand
successive lightning attack.
l
Common mode and differential mode protection, and low residual voltage.
l
Dual-color working status indication, with remote alarm node.
l
Small in size and easy installation.