User Manual
Airbridge cBTS3612 CDMA Base Station
System Description
2 Hardware Architecture
2-53
l
Output voltage: +27
!
0.5V
l
Output voltage range: +25~+29VDC
l
Output over-voltage protection point: +30.5
!
0.5VDC
l
DC output rated current: 65A
l
Output current-limiting point: 68.5~71.5A
l
Regulated voltage precision:
Ÿ!
1%
Load regulation:
Ÿ!
0.5%
Voltage regulation:
Ÿ!
0.2%
l
Output noise voltage
Balanced noise of phone:
Ÿ
2.0mV (300~3400Hz)
Broadband noise voltage:
Ÿ
30mV (3.4k~30MHz)
Peak-peak value noise voltage:
Ÿ
100mV (0~20MHz)
Discrete noise voltage:
Ÿ
5mV (3.4kHz~150kHz )
Ÿ
3mV (150kHz~200kHz)
Ÿ
2mV (200kHz~500kHz)
Ÿ
1mV (500kHz~30MHz)
l
Power efficiency:
¦
85% (in full load)
l
Dynamic performance
Load effect recovery time:
Ÿ
200
µ
s 25%~50%~25% load variance
50%~75%~50% load variance
Output overshoot:
Ÿ
5% output voltage setting value
l
Equipment delay:
Ÿ
5s
l
Safety requirement
Insulation resistance of input-case, input -output, output-case:
¦
2 M Ù
Test conditions: ambient temperature: 20
!
5
â
C
Relative humidity: 90%
Test voltage: DC 500V
l
Insulation strength
Input -output: AC 1000V/1min/30mA
Input -ground: AC 500V/1min/30mA
Output-ground: AC 500V/1min/30mA