C. Suggested Corrective Actions

Problem

Possible Causes

Possible Remedies

No electrical power to the water 

heater

1. Is the plug on the power supply cord unplugged 

from the electrical outlet?

2. Is the circuit breaker tripped?

3. Is the fuse on the circuit board good?

4. Is there a power outage to the home?

1. Reset the plug.

2. Reset the circuit breaker.

3. If the display panel is blank, unplug the unit or 

contact an authorized service technician.

4. Contact the power company.

No water available when faucet 

is opened

1. Is the water supply valve shut off at the meter (do 

cold water faucets work)?

2. Is the water supply valve near the unit open?

3. Is the water pipe frozen?

4. Is an error code flashing on the display panel (leak 

detected)?

1. Open the closed supply valve.

2. Open the water supply valve.

3. Turn OFF the unit, close all water valves and 

the gas valve. Contact an authorized service 

technician.

4. Refer to error code information and contact an 

authorized service technician.

Hot water is not available when 

a faucet is opened

1. Does the water heater have power (plugged in)?

2. Is the water heater turned ON?

3. Is an error code flashing on the display panel?

4. Is the gas supply valve open or shut off at the 

meter (do other gas devices work)?

1. Restore electrical power to the unit.

2. Press and hold the Power button to turn the 

unit ON.

3. Refer to the Diagnostic and Error Codes section 

in this manual.

4. Open the gas supply valve.

The water temperature is not hot 

enough or turns cold during use

1. Is an error code flashing on the display panel?

2. Is the outlet water temperature set too low?

1. Open the faucet to allow more water flow.

2. Refer to the Diagnostic and Error Codes section 

in this manual.

3. Adjust the outlet water temperature (refer to 

the procedure in this manual).

It takes a long time before hot 

water flows from the faucet

Is the faucet some distance from the water heater?

1. Install a recirculation line.

2. Allow time for the cold water already in the 

pipes to flow from the faucet.

The water is not hot enough

Is the water temperature set too low?

Adjust the temperature setting.

The water at the faucet is too hot Is the water temperature set too high?

Adjust the temperature setting.

A fan can be heard even when 

the unit is not operating

1. The fan operates after the burner shuts off to clear 

combustion gases from the exhaust vent.

2. The fan may run to help prevent freezing.

1. This is normal operation – no action is required.

2. Protect the water heater from freezing 

temperatures or shut off and drain the unit.

White “smoke” can be seen 

coming out of the exterior 

exhaust gas vent

Depending on the outside temperature, water 

vapor can be produced as the exhaust is vented.

This is normal operation – no action is required.

Table 30 - Troubleshooting Chart

DIAGNOSTICS AND SUGGESTED CORRECTIVE ACTIONS

The water heater control is able to record information about the water heater’s condition at the time of the ten previous faults or errors. This 

information is available to view in the Installer Mode under the History screen.

The following screens may be displayed when reviewing the water heater history. The table below also includes diagnostic information and 

possible corrective actions.

Display

Condition

Diagnostic

Possible Corrective Actions

Nothing appears 

on the display but 

the fan runs at full 

speed

Control is not 

receiving power

Check for incorrect or short circuited wiring 

Correct wiring per wiring diagram including 

connection of transformer to the control.

Check transformer connection to the control 

per wiring diagram. Check for 14V output of 

panel wire.

Push the Power button on the control panel

Nothing appears 

on the display 

control panel 

and no other 

water heater 

components are 

operating

Control is not 

receiving 120V 

power

Ensure service switch and/or circuit breaker 

to water heater is turned ON

Turn on service switch or circuit breaker to 

power water heater

Is there 120V at the service switch

Troubleshoot and correct the power supply to 

the manual switch

Is the ON/OFF switch inside the water heater 

cabinet is turned on

Turn ON the manual power switch inside the 

water heater cabinet

Check for 120V at the line voltage terminal 

block located inside the water heater cabinet

Correct wiring inside the heater cabinet using 

the wiring diagram in the installation manual

Inspect the fuse. Replace as necessary

Replace the fuse. See replacement parts 

section for part number. If fuse blows again, 

recheck the wiring per diagram.

Содержание CGH-199O Series

Страница 1: ...UCTIONS FOR FUTURE REFERENCE 272 Duchaine Blvd New Bedford MA 02745 www htproducts com lp 673 Rev 000 Rel 001 Date 8 30 18 The surfaces of these products contacted by potable consumable water contain...

Страница 2: ...ices not related to personal injury WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not stor...

Страница 3: ...est version from Canadian Gas Association Laboratories 55 Scarsdale Road Don Mills Ontario Canada M3B 2R3 Also Canadian Electrical Code C 22 1 from Canadian Standards Association 5060 Spectrum Way Sui...

Страница 4: ...ance 56 Part 13 Replacement Parts 59 Limited Warranty for RGH Water Heaters 65 Notes 67 Customer Installation Record Form 68 Part 1 General Safety Information This water heater is approved for outdoor...

Страница 5: ...on and the placement of critical components circulators condensate neutralizers etc before installing the water heater DO NOT allow children to operate this unit DO NOT use this unit if it does not ap...

Страница 6: ...er supplied from utility or well water in compliance with EPA secondary maximum contaminant levels 40 CFR Part 143 3 If the water contains contaminants higher than outlined by the EPA water treatment...

Страница 7: ...seconds 150oF About 1 1 2 seconds 155oF About 1 second Table 3 Time and Temperature Relationship in Scalds Households with small children disabled or elderly persons may require a 120o F or lower tem...

Страница 8: ...cations where rain from building runoff may spill onto the heater Doing so could result in premature product failure Such failures ARE NOT covered by warranty Do not locate where sprinklers may spray...

Страница 9: ...er and energy insulate all water piping especially the hot and recirculation water lines Table 6 Minimum Installation and Service Clearances Recommended Service and Proper Operation Clearances Top 36...

Страница 10: ...r heater by any means other than those described in this manual Doing so will void the warranty and may result in severe personal injury or death Failure to vent the water heater properly will result...

Страница 11: ...ng Photo processing plants Refrigerant leaks Auto body shops Paint or varnish removers Plastic manufacturing plants Hydrochloric or Muriatic acid Furniture refinishing areas and establishments Cements...

Страница 12: ...Electronic Ignition Automatic Flame Sensing Burner System Single Orifice Premixed Fuel Modulation Ceramic Fiber Burner Gas Valve System Air Ratio Valve Minimum Flow Rate Zero activation with storage...

Страница 13: ...external mixing valve and increasing tank setpoint temperature Example If installation requires 120F from Mixing Valve set tank at 140F to increase First Hour Rating Peak Hour Demand First Hour Ratin...

Страница 14: ...Intake B Exhaust Vent C DHW Outlet Adapter 1 1 4 NPT D DHW Inlet Adapter 1 1 4 NPT E Gas Inlet Adapter 3 4 NPT F Condensate Adapter 1 2 NPT 3 4 PVC Socket on Floor Models Table 13 Adapter Specificatio...

Страница 15: ...Heat Exchanger The highly efficient 316L stainless steel fire tube heat exchanger with internal aluminum is designed to extract all available heat from the combustion process and pass it into heat tra...

Страница 16: ...ected units up or down to ensure the units are putting only the needed energy into the connected storage tank and also to ensure all connected units get even run time to balance out service requiremen...

Страница 17: ...xpansion tank In the hot outlet install a suitable adapter to match the tubing of B Backflow Preventer Use a backflow preventer specifically designed for water heater installations This valve should b...

Страница 18: ...ower to the water heater or isolate the heater from the system if ANY plumbing work is to be done Running the water heater without water will result in dry firing 9 The setpoint of the water heater ne...

Страница 19: ...ent scalding 8 Always shut off power to the water heater or isolate the heater from the system if ANY plumbing work is to be done Running the water heater without water will result in dry firing 9 The...

Страница 20: ...vacuum relief valve per 248 CMR 7 Mixing valve application is optional but recommended to help prevent scalding 8 Always shut off power to the water heater or isolate the heater from the system if ANY...

Страница 21: ...ng 8 Always shut off power to the water heater or isolate the heater from the system if ANY plumbing work is to be done Running the water heater without water will result in dry firing 9 The setpoint...

Страница 22: ...ust be installed as close to the water heater as possible No other valves should be placed between the pressure relief valve and the appliance DO NOT install a relief valve with a pressure rating grea...

Страница 23: ...ot attempt to conduct an inspection on your own Contact your plumbing contractor for a re inspection to assure continued safety Do not thread a cap or plug into the relief valve or relief valve line u...

Страница 24: ...Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the center line of the terminal E Clearance to unventilated soffit F Clearance to outside...

Страница 25: ...on The flue products from the exhaust vent will create a large plume when the heater is in operation Avoid venting in areas that will affect neighboring buildings or be considered objectionable DO NOT...

Страница 26: ...re the unit exhaust extends level with or above the top of the fence to ensure flue gas does not get trapped and possibly recirculated into the louver system which could contaminate the combustion air...

Страница 27: ...nsate line from freezing temperatures or any type of blockage In installations that Figure 20 Condensate Piping with 1 Neutralizer to Drain and 2 Neutralizer to Pump may encounter sustained freezing c...

Страница 28: ...3 Factory Factory Settings DO NOT CHANGE 4 Vent Size Factory Settings DO NOT CHANGE 5 Gas Type LP NG 6 High Fire Normal High Fire 7 Low Fire Normal Low Fire Table 18 DIP Switch Group NOTE DO NOT CHAN...

Страница 29: ...If the 0 10V is connected the Master control will calculate the water temperature set point based on the programmed reset curve parameters If the 0 10V is not connected the Master control will mainta...

Страница 30: ...lp 673 Rev 000 Rel 001 Date 8 30 18 30 Figure 31 Electrical Wiring Diagram...

Страница 31: ...lp 673 Rev 000 Rel 001 Date 8 30 18 31 Figure 32 Ladder Diagram...

Страница 32: ...3WAY NOT USED 3 NOT USED CN1 SMW250 03 1 RS 485 RS 485 Cascade Connection SELV 5V DC 2 RS 485 3 4 RS 485 5 RS 485 CN4 LWD1140 06 1 FAN NOT USED 2 GND 3 VDD SELV 14V DC 4 Fan power start coil SELV 8 2...

Страница 33: ...BTU ft3 Contact the local gas supplier for actual BTU ft3 rating 2 Natural Gas Pipe Sizing The following table lists maximum capacity of pipe in cubic feet of gas per hour for gas pressures of 14 or l...

Страница 34: ...FV isinthegasline checkthemanufacturer s minimum and maximum flow capacity ratings An improperly sized EFV will not allow for a full flow of gas to the water heater and will cause the water heater to...

Страница 35: ...play Overviews Press this Button Less than 5 Seconds Turns Control Power Panel ON OFF Hold this Button More than 5 Seconds When Control Panel Power is ON Status Display Mode When Control Panel Power i...

Страница 36: ...re bathing or showering D Changing the Time Press and hold the button for five seconds when the display panel is powered ON to change the time The settings can be adjusted as follows Year Month Date H...

Страница 37: ...in 1000 hour units 2 rh Burner operating time Time burner has operated in 1 hour units 3 rH Burner operating time Time burner has operated in 1000 hour units 4 It Ignition attempts Number of ignition...

Страница 38: ...ets Maximum Storage Tank Temperature Range rE 95 140oF or Co 95 160oF 11 dd 7F Storage Tank Differential Set Point Storage Tank Differential Set Point Range 5 30o F 12 Pr 1 MIN System and Heater Pump...

Страница 39: ...the button again The display will return to power off mode G Setting Up a Cascaded System For each floor containing bedroom s a carbon monoxide detector and alarm shall be placed in the living area ou...

Страница 40: ...ntrol the set point temperature of the water heater The control interprets the 0 10 volt signal as follows when the signal is between 0 and 1 5 volts the water heater will be in standby mode not firin...

Страница 41: ...g settings are more than 2 5DC before ignition less than 2 5DC after ignition 4 Check igniter transformer for proper connection 5 Clean the spark igniter with steel wool to remove oxides Ensure proper...

Страница 42: ...1 Check DHW sensor If an aquastat ensure AquA is selected in Installer Mode 39 If a sensor ensure connections are secure 2 Check DHW sensor resistance If resistance is zero or does not match that in T...

Страница 43: ...r 4 Consecutive Times This Error Code will go away when the condition is remedied If Error happens again 1 Ensure all valves are open to the water heater and there are no leaks 2 Ensure all air has be...

Страница 44: ...1 Flame Detection Figure 45 Flame Detection Error Analysis Tree 2 Air Pressure Switch Detection Figure 46 Air Pressure Switch Analysis Tree 3 Inlet DHW Operating Temperature Exhaust Sensors Figure 47...

Страница 45: ...s too hot Is the water temperature set too high Adjust the temperature setting A fan can be heard even when the unit is not operating 1 The fan operates after the burner shuts off to clear combustion...

Страница 46: ...h the propane to make its presence detectable In some instances the odorant can fade and the gas may no longer have an odor Before startup and periodically thereafter have the propane supplier verify...

Страница 47: ...run is used it may be necessary to create a vent in the horizontal run to prevent a vacuum lock in the condensate line 4 Do not expose the condensate to freezing temperatures 5 It is very important yo...

Страница 48: ...line a minimum of 3 4 in diameter Is the gas supply line length and diameter adequate to deliver the required BTUs Has gas supply line pressure been measured Does the gas type match the type indicated...

Страница 49: ...f blockage leakage or deterioration of the piping Inspect the exhaust vent bracing Ensure bracing is undamaged and in good condition Notify a qualified service technician immediately if any problems a...

Страница 50: ...Use a NIOSH certified dust respirator N95 This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written Other types of respirators may be needed dep...

Страница 51: ...d Exercise circuit breaker Switch and Plug Verify ON OFF switch and convenience plug are both functional CHAMBER BURNER Combustion Chamber Check burner tube and combustion chamber coils Clean accordin...

Страница 52: ...ird Screen Screw 7855P 664 B 8 M4 X 10 Flat Head 7855P 391 B 19 6 20 x 1 2 Self Drilling Screw 7350P 400 B 9 M4 X 12 PH M S 7855P 392 B 20 M5 X 12MM PH Screw 7865P 023 B 10 M4 X 12 TH M S 7855P 393 N...

Страница 53: ...Stand 7865P 004 4 2 Vent Pipe Assembly 7860P 100 15 Condensate Hose 7855P 089 5 Outdoor Vent Pipe Bracket 7855P 662 16 Pump Assembly 7860P 103 6 Outdoor Top Cover 7855P 623 17 Back Panel Floor Stand 7...

Страница 54: ...acket 7850P 068 11 Terminal Blocks Bracket 7855P 434 3 Bottom Wall Mount Bracket 7850P 092 12 Control Board 7855P 408 4 Air Vent 7855P 063 13 Display Panel 7860P 006 5 Air Vent Adapter 7855P 454 14 Ma...

Страница 55: ...7855P 357 32 Heat Exchanger Assembly 7860P 011 37 Outlet Pipe 7860P 012 32 1 Burner Body Assembly 7855P 417 37 1 Outlet Pipe Gasket 7855P 074 32 2 Burner Overheat Switch 7855P 066 38 Inlet Pipe 7855P...

Страница 56: ...26 55 3 Gas Valve 7855P 034 50 Fan and Mixer Assembly 7855P 427 55 4 Gas Valve Inlet Adapter 7850P 077 50 1 Fan 7855P 025 55 5 Gas Valve Bracket 7855P 436 50 2 Fan O Ring 7855P 371 56 1 2 Gas Pipe Gas...

Страница 57: ...closed system with a properly sized and installed thermal expansion tank 6 Use the water heater at water pressures not exceeding the working pressure shown on the rating plate 7 Keep the water heater...

Страница 58: ...o HTP the returned product must arrive at HTP within thirty 30 days of the date of our request to return the product After receipt of the returned product HTP may require as many as thirty 30 addition...

Страница 59: ...lp 673 Rev 000 Rel 001 Date 8 30 18 59 Notes...

Страница 60: ...e Date of Installation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Cust...

Отзывы: