3.  SIGNAGE.  A metal or plastic identification plate shall be permanently mounted to the 

exterior of the building at a minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled heating appliance or 

equipment.  The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT 

DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”. 

4.  INSPECTION.  The state or local gas inspector of the side wall horizontally vented gas 

fueled equipment shall not approve the installation unless, upon inspection, the inspector 

observes carbon monoxide detectors and signage installed in accordance with the 

provisions of 248 CMR 5.08 (2)(a) 1 through 4. 

(b) EXEMPTIONS:  the following equipment is exempt from 248 CMR 5.08 (2)(a) 1 through 4: 

1.  The equipment listed in Chapter 10 entitled “Equipment Not Required to be 

Vented” in the most current edition of NFPA 54 as adopted by the Board; and 

2.  Product Approved side wall horizontally vented gas fueled equipment installed in a 

room or structure separate from the dwelling, building or structure used in whole or in 

part for residential purposes. 

(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED.  When 

the manufacturer of Product Approved side wall horizontally vented gas equipment 

provides a venting system design or venting system components with the equipment, the 

instructions provided by the manufacturer for installation of the equipment and the venting 

system shall include: 

1.  Detailed instructions for the installation of the venting system design or the venting 

system components; and 

2.  A complete parts list for the venting system design or venting system. 

(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.  

When the manufacturer of a Product Approved side wall horizontally vented gas fueled 

equipment does not provide the parts for venting the flue gases, but identifies “special 

venting systems”, the following requirements shall be satisfied by the manufacturer: 

1.  The referenced “special venting system” instructions shall be included with the 

appliance or equipment installation instructions; and 

2.  The “special venting systems” shall be Product Approved by the Board, and the 

instructions for that system shall include a parts list and detailed installation instructions. 

(e)  A copy of all installation instructions for all Product Approval side wall horizontally vented 

gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all 

venting design instructions shall remain with the appliance or equipment at the completion 

of the installation. 

Содержание CG N65 Series

Страница 1: ...l injury or death HTPreservestherighttomakeproductchangesorupdateswithoutnoticeandwillnotbeheldliablefortypographical errors in literature NOTETO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFER...

Страница 2: ...CINITY OFTHIS OR ANY OTHER APPLIANCE WHATTO DO IFYOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediately call your gas supp...

Страница 3: ...dividual such as a fire chief fire marshal chief of a fire prevention bureau labor department or health department building official or For the Installer This water heater must be installed by qualifi...

Страница 4: ...RSONAL INJURY OR DEATH DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN SUBMERGED IN WATER Immediately call a qualified service technician The water heater MUST BE replaced if it has been submerged A...

Страница 5: ...require a 120oF or lower temperature setting to prevent severe personal injury or death due to scalding F Water Temperature Adjustment If the water heater is going to have a set temperature above 120...

Страница 6: ...DS concentration will greatly accelerate lime and scale formation in the hot water system Most high TDS concentrations precipitate out of the water when heated This can generate a scale accumulation t...

Страница 7: ...water heater See Figure 13 for proper installation The drain pan should be at least 4 10 2 cm larger than the diameter of the water heater and at least 1 2 5 cm deep providing access to the drain val...

Страница 8: ...dern buildings additional fresh air may need to be provided For instructions on obtaining additional air supply see the requirements for confined spaces 2 Requirements for Confined Spaces In the US re...

Страница 9: ...for all the appliances installed in that confined space See Figure 7 When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The mini...

Страница 10: ...afthood assembly is installed Failure to follow these instructions can result in property damage personal injury or death When installing the water heater make sure the location allows clear viewing o...

Страница 11: ...stallation with a TjernlundTM side wall power vent kit See Figure 10 This kit can be installed as part of a new installation or retrofitted onto an existing installation The kit consists of a power ve...

Страница 12: ...tally L Clearance above paved sidewalk or paved driveway located on public property 7 2 13 m M Clearance under veranda porch deck or balcony 12 Table 3 Side Wall PowerVentTermination Requirements 1In...

Страница 13: ...ssure and or temperature the manufacturer has installed a temperature and pressure relief valve that meets the requirements of the Standard for Relief Valves and Automatic Gas Shut Off Devices for Hot...

Страница 14: ...ates or CAN CSA B149 1 NationalGas and Propane InstallationCode in Canada Only new piping with cleanly cut threads may be used The water heater and its gas connection must be leak tested before placin...

Страница 15: ...ly manual shut off valve must be closed NOTE Theinputratingoftheapplianceisbasedoninstallation and operation at sea level up to elevations of 2 000 ft Low NOx models are certified to operate to 2 000...

Страница 16: ...o disconnecting Verify all wiring connections before relighting the water heater Wiring errors can result in property damage personal injury or death Damages to this product due to improper wiring ARE...

Страница 17: ...LP 436 Rev 5 20 15 17 Figure 17 Wiring the Control...

Страница 18: ...nections been properly installed and are they leak free Is the water heater full of water Gas Connections Complete Is the gas supplied to the water heater the same type indicated on the water heater r...

Страница 19: ...ures at the hot water outlet Always remember to check the hot water coming out of any faucet with your hand before use This will reduce the risk of scalding related injury Figure 18 Thermostat D Out o...

Страница 20: ...erly refer to Drafthood Operation G Anode This water heater is equipped with multiple anode rods that are designed to prolong the life of the glass lined tank By the electrolytic action these anodes a...

Страница 21: ...ater follow these two easy steps 1 Consult the Troubleshooting Guide in this manual It will guide you to the most common problems experienced with a gas fired water heater The solutions you find liste...

Страница 22: ...019 16 Access Door 8800P 018 17 Outlet Nipple 8800P 032 18 Nipple Temperature and Pressure ReliefValve 8800P 033 8800P 034 19 Temperature and Pressure ReliefValve 8800P 035 8800P 036 20 Anode 8800P 03...

Страница 23: ...water heater The diagnostic system is designed to give the user or qualified service technician a visual indication of the operational status of the different parts of the water heater s control syste...

Страница 24: ...LP 436 Rev 5 20 15 24...

Страница 25: ...LP 436 Rev 5 20 15 25...

Страница 26: ...LP 436 Rev 5 20 15 26...

Страница 27: ...LP 436 Rev 5 20 15 27...

Страница 28: ...LP 436 Rev 5 20 15 28...

Страница 29: ...OXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an...

Страница 30: ...TING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instruct...

Страница 31: ...at optimum efficiency 2 Maintain all related heating components in good operating condition 3 Use the water heater in an open system with a properly sized and installed thermal expansion tank 4 Use th...

Страница 32: ...is denied If all warranty conditions are satisfied HTP will provide replacement parts to the retailer For questions about the coverage of this warranty please contact HTP at the address or phone numbe...

Страница 33: ...LP 436 Rev 5 20 15 33 Maintenance Notes...

Страница 34: ...f Installation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Ple...

Отзывы: